- DeviceNet
-
DeviceNet is a network system used in the automation industry to interconnect control devices for data exchange. It uses Controller Area Network as the backbone technology and defines an application layer to cover a range of device profiles. Typical applications include information exchange, safety devices, and large I/O control networks. [1][2]
Contents
History
DeviceNet was originally developed by American company Allen-Bradley (now owned by Rockwell Automation). It is layered on top of the CAN (Controller Area Network) technology, developed by Bosch.[3] DeviceNet adapts the technology from ControlNet, which is another industrial protocol developed by Allen-Bradley, and takes advantage of CAN, making it low-cost and robust compared to the traditional RS-485 based protocols.
In order to promote the use of DeviceNet worldwide, Rockwell Automation has adopted the "open" concept and decided to share the technology to third party vendors. Hence, it is now managed by the Open DeviceNet Vendors Association (ODVA), an independent organization located in North America. ODVA maintains specifications of DeviceNet and oversees advances to DeviceNet. In addition, ODVA ensures compliance to DeviceNet standards by providing conformance testing and vendor conformity.[3]
ODVA later decided to bring DeviceNet back to its predecessor's umbrella and collectively call the technology as Common Industrial Protocol or (CIP), which includes the following technologies:
- EtherNet/IP (take note of the capital 'N', and "IP" here means "Industrial Protocol")
- ControlNet
- DeviceNet
- CompoNet
ODVA claims high integrity between the three technologies due to the common protocol adaptation, which makes industrial controls much simpler compared to other technologies.
Technical Snapshot
- Defines the Media, Physical, Data-Link, and Application layers of the ISO/OSI 7-layer model (see Open Systems Interconnection)
- Incorporates trunkline topology with separate buses for signal and power (Typical configuration: two twisted pairs and a single shield)
- Baudrates defined: 125 kbit/s, 250 kbit/s, and 500 kbit/s
- Trunk length is inversely proportional to the speed, i.e. 500, 250 and 100 meters respectively
- A not-so new flat cable was added to the specification to allow the use of the quick-fix connector
- Up to 64 nodes on a single logical network. (Node addresses range from 0 - 63) The network has a low node priority scheme
- Supports master/slave as well as peer-to-peer communication, although majority of the devices work in the master/slave configuration
- Allows multiple masters on a single logical network
- Network cable can supply device power along same cable as communication cable (Generally smaller devices such as photo-eyes, limit switches, and proximity switches).
- Networked devices can be simultaneously controlled and configured
- Engineered to withstand noisy environments
- Supports 4 message types to/from slave devices (Strobed, Polled, Cyclic, COS (change of state)). Some devices support more than 1 message type
Architecture
Physical Layer
Nodes are distributed along a DeviceNet network by the means of a trunkline-dropline topology. This topology allows for ease in wiring and access to the network from multiple taps. In addition, nodes can be easily removed and added to reduce production downtime, increase network flexibility, and decrease troubleshooting time. Since the physical layer is optically isolated from device, communication power and device power can share the same bus (Further reducing the complexity of the network and components within). ( Introduction[5])
DeviceNet supports 125 kbit/s, 250 kbit/s and 500 kbit/s data rates. Depending on the chosen cable type, DeviceNet can support communication up to 500 meters (Round thick cable). Typical round cable supports up to 100 meters. While flat style cable supports up to 380 meters at 125 kbit/s and 75 meters at 500 kbit/s.( Physical Layer [5])
Data Link Layer
DeviceNet uses a differential serial bus (Controller Area Network) as its Data Link Layer. Using CAN as a backbone, DeviceNet requires minimal bandwidth to transmit and package messages. In addition, a smaller processor may be selected in the design of device thanks to data frame format and the ease at which the processor can parse through the data. See below for full format.( The Data Link Layer[5])
CAN Data Frame Format
1 Bit => Start of Frame 11 Bits => Identifier 1 Bit => RTR Bit 6 Bits => Control Field 0-8 Bytes => Data Field 15 Bits => CRC Sequence 1 Bit => CRC Delimiter 1 Bit => Acknowledge 1 Bit => Ack Delimiter 7 Bits => End of Frame >2 Bits => Interframe Space
Reference: Table: Data Frame Format.[5]
Upon transmitting the first packet of data, the "Start of Frame" bit is sent to synchronize all receivers on the network. The CAN identifier (denoted from 0-63) and RTR bit combine to set priority at which the data can be accessed or changed. Lower identifiers have priority over higher identifiers. In addition to transmitting this data to other devices, the device also monitors the data sent. This redundancy validates the data transmitted and eliminates simultaneous transmissions. If a node is transmitting at the same time as another node, the node with the lower 11 bit identifier will continue to transmit while the device with the higher 11 bit identifier will stop.(Introduction & Physical Layer.[5])
The following 6 bits contain information for specifying the Control Field. The initial two bits are fixed, while the last four are used to specify length field of the Data Field. The Data Field contains from zero to eight bytes of usable data.(Physical Layer.[5])
The following data frame is the CRC (Cyclic Redundancy Check) Field. The frame consists of 15 bits to detect frame errors and maintains numerous format delimiters. Due to ease of implementation and immunity to most noisy networks, CAN provides a high level of error checking and fault confinement.(Physical Layer.[5])
Network
DeviceNet incorporates a connection-based network. A connection must initially be established by either an UCMM (Unconnected Message Manager) or a Group 2 Unconnected Port. From there, Explicit and Implicit messages can be sent and received. Explicit messages are packets of data that general require a response from another device. Typical messages are configurations or non-time sensitive data collection. Implicit messages are packets of data that are time critical and generally communicate real-time data over the network. An Explicit Message Connection has to be used to established first before an Implicit Message Connection is made. Once the connection is made, the CAN identifier routes data to the corresponding node.(The Network and Transport Layers.[5])
Conformance Test
To declare your product as DeviceNet compatible, a vendor needs to send their product to the ODVA test lab for the certification. ODVA used to have a few other test labs around the world, i.e. UK, Japan, and China. It has since been consolidated into one facility in North America.[6]
A full-test version is called the Composite test. It consists of:[7]
- Conformance test. Test against the protocol specification.
- Interoperability test. Test against devices from various vendors on a single, fully populated, network.
Conformance Test Procedure
The following procedure shows you how to get your product certified.
- Register as vendor with ODVA. You will be given a vendor ID.
- Purchase a copy of the DeviceNet specification. A hard and soft copy will be sent to you.
- Purchase the conformance test software and corresponding hardware interface card. Note that only selected interface cards from a few vendors can be used.
- Develop and test product in-house. You would probably need help from the discussion group, see the External links below.
- Submit your product to ODVA test lab for independent verification.
- Repeat the above two steps until your product successfully pass the independent test.
Reference[8]
See also
External links
Sources
Notes
- ^ [1] Controller Area Network Solutions FAQ (Frequently Asked Questions).
- ^ a b [2], DeviceNet Technology Overview.
- ^ a b [3] Controller Area Network Solutions FAQ (Frequently Asked Questions)], What is DeviceNet?.
- ^ [4] Controller Area Network Solutions FAQ (Frequently Asked Questions)], Basic DeviceNet Concepts?.
- ^ a b c d e f g h "DeviceNet Technical Overview" from Open DeviceNet Vendor Association, Inc. (ODVA)
- ^ [5], Conformance Testing.
- ^ [6], Conformance Testing.
- ^ [7], Conformance Testing.
Automation protocols Process automation - BSAP
- CC-Link Industrial Networks
- CIP
- Controller area network
- ControlNet
- DeviceNet
- DF-1
- DirectNET
- EtherCAT
- Ethernet Global Data (EGD)
- Ethernet Powerlink
- EtherNet/IP
- FINS
- FOUNDATION fieldbus (H1, HSE)
- GE SRTP
- HART Protocol
- Honeywell SDS
- HostLink
- INTERBUS
- MECHATROLINK
- MelsecNet
- Modbus
- Optomux
- PieP
- Profibus
- PROFINET IO
- SERCOS interface
- SERCOS III
- Sinec H1
- SynqNet
- TTEthernet
Industrial control system Building automation Power system automation - IEC 60870-5
- DNP3
- IEC 60870-6
- IEC 61850
- IEC 62351
- Modbus
- Profibus
Automatic meter reading - ANSI C12.18
- IEC 61107
- DLMS/IEC 62056
- M-Bus
- Modbus
- ZigBee Smart Energy 2.0
Automobile / Vehicle Categories:- Industrial computing
- Production and manufacturing
- Serial buses
- Industrial automation
Wikimedia Foundation. 2010.