- High voltage switchgear
High voltage switchgear is any
switchgear used to connect or disconnect a part of a high-voltage power system. Theseswitchgear are essential elements for the protection and safe operation, without interruption, of a high voltage power system. This type of equipment is important because it is directly linked to the quality of the electricity supply.The
International Electrotechnical Commission defines "high voltage" as avoltage above 1,000Volt s foralternating current and above 1500 V fordirect current .High voltage switchgear was invented at the end of the
19th century for operating motors and others electric machines [en [http://v3.espacenet.com/origdoc?DB=EPODOC&IDX=GB189320069&F=0&QPN=GB189320069 British Pattern GB 20069 "Improvements in Apparatus for Controlling the Application or Use of Electric Currents of High Tension and Great Quantity" in 1893] , on espacenet.com] . The technology has been improved over time and can be used with voltages up to 1100 kV en Lin Jiming et al., "Transient characteristics of 1 100 kV circuit-breakers", "International Symposium on International Standards for Ultra High Voltage", Beijing, Juillet 2007.] .Classification
Functional Classification
Disconnectors and earthing switches
Disconnectors and earthing switches are safety devices used to open or to close a
circuit when there is no current through them. They are used to isolate a part of a circuit, a machine, a part of an overhead line or an underground line so that maintenance can be safely conducted.The opening of the line
isolator orbusbar section isolator is necessary for safety, but not sufficient. Grounding must be conducted at both the upstream and downstream sections of the device under maintenance. This is accomplished by earthing switches.In principle, disconnecting switches do not have to interrupt currents, as they are designed for use on de-energized circuits. In practice, some are capable of interrupting currents (as much as 1600 amps under 300 V but only if current is drawn via a same circuit half breaker bypass system), and some earthing switches must interrupt induced currents which are generated in a non-current-carrying line by inductive and capacitive coupling with nearby lines (up to 160 A under 20 kV) ) [fr [http://domino.iec.ch/preview/info_iec62271-102{ed1.0}b.pdf "IEC 62271-102 for A.C. disconnectors and earthing switches"] ] .
High-current switching mechanism
High-current switching mechanisms are used for energized circuits carrying a normal load. Some can be used as a disconnecting switch.
However, if they can create a short-circuit current, they can not interrupt it [fr [http://domino.iec.ch/preview/info_iec60265-1{ed3.0}b.pdf "Norme CEI 60265-1 Interrupteurs pour tension assignée supérieure à 1 kV et inférieure à 52 kV"] ] [fr [http://domino.iec.ch/preview/info_iec60265-2{ed1.0}b.img.pdf "Norme CEI 60265-2 Interrupteurs pour tension assignée supérieure à 52 kV] ] .
Contactor
Contactors are similar in function to high-current switching mechanisms, but can be used at higher rates. They have a high electrical endurance and a high mechanical endurance [fr [http://domino.iec.ch/preview/info_iec60470{ed2.0}b.pdf Norme CEI 60470 "Contacteurs pour courant alternatif haute tension et démarreurs de moteurs à contacteurs"] ] .
Contactors are frequently used to operate devices like electric furnaces and high voltage motors. They can not be used as a disconnecting switch.
They are used only with high voltages in the range of 30 kV to 100 kVFact|date=September 2008.
Fuses
A fuse can automatically interrupt a circuit with an overcurrent flowing in it for a fixed time. This is accomplished by the fusion of an
electrical conductor which is graded.Fuses are mainly used to protect against
short circuit s. They limit the peak value of the fault current.In
three-phase electric power , they only eliminate the phases where the fault current is flowing, which can pose a risk for both the malfunctioning devices and the people. To alleviate this problem, fuses can be used in conjunction with high-current switches or contactors.Like contactors, high-voltage fuses are used only in the band 30 kV to 100 kVFact|date=September 2008.
Circuit Breaker
A high voltage
circuit breaker is capable of connecting, carrying and disconnecting currents under the ratedvoltage (the maximal voltage of the power system which it is protecting).Under normal operational conditions, circuit breakers can be used to (dis)connect a line. Circuit breakers can also be used to interrupt current when anomalies are detected, such as a short-circuit.
Circuit breakers are essential elements of high-voltage power systems because they are the only means to safely interrupt a short circuit current. The international standard IEC 62271-100 defines the demands linked to the characteristics of a high voltage circuit breaker [fr [http://domino.iec.ch/preview/info_iec62271-100{ed1.2}b.pdf "Norme CEI 62271-100 Disjoncteurs à haute tension"] ] .
The circuit breaker can be equipped with electronic devices in order to know at any moment their states, such as wear or gas pressure, and to detect faults from characteristic derivatives. It can also permit planned maintenance operations and to avoid failures. [ frE.Thuries, G.Ebersohl, J.P.Dupraz, O.Chetay, J.P.Montcorgé, "Introduction de l'électronique numérique dans les auxiliaires de l'appareillage et amélioration de la fiabilité", 1994, CIGRE session 1994, rapport 23/13-09] frDenis Dufournet, "Disjoncteurs SF6 - Évolution de 1959 à 1994, 1994", "Revue générale de l'électricité" n° 5] .
To operate on long lines, circuit breakers are equipped with a closing
resistor to limitovervoltage s [ en D.E. Heldman, I.B. Johnson, C.H. Titus, D.D. Wilson, "Switching of Extra-High-Voltage Circuits, Surge reduction with circuit-breaker resistors", 1964, "IEEE Transactions on Power Apparatus and Systems", Vol. 83 (1964-12)] [frEugène Maury, "Problèmes apparaissant aux tensions les plus élevées lors de la manœuvre des disjoncteurs", 1964, CIGRE session 1964] .They can be equipped with devices to synchronize closing and/or opening, to limit the overvoltages and the inrush currents from the lines, the unloaded
transformer s, the shunt reactances and thecapacitor banks [frEugène Maury, "La fermeture synchronisée des disjoncteurs 525 kV et 765 kV, moyen de réduire les surtensions de manœuvre sur lignes à vide", 1966, CIGRE session 1966.] [en Groupe de travail CIGRE 13.07, "Controlled switching of HV AC circuit breakers", 1999, "Electra" N° 183] .Some devices are designed to have the characteristics of the circuit breaker and the disconnector [fr [http://webstore.iec.ch/preview/info_iec62271-108%7Bed1.0%7Db.pdf "Norme CEI 62271-108 Disjoncteur-sectionneurs"] ] , but their use is not widespread.
See also
*
Switchgear References