- Natural ventilation
-
Natural ventilation is the process of supplying and removing air through an indoor space without using mechanical systems. It refers to the flow of external air to an indoor space as a result of wind or temperatures differences. There are two types of natural ventilation occurring in buildings: wind driven ventilation and stack ventilation. While wind is the main mechanism of wind driven ventilation, stack ventilation occurs as a result of the directional buoyancy force that results from temperature variation. [1] The pressures generated by buoyancy, also known as 'the stack effect', are quite low (typical values: 0.3 Pa to 3 Pa) while wind pressures are usually far greater (~1 Pa to 35 Pa). The majority of buildings employing natural ventilation rely primarily on wind driven ventilation, but stack ventilation has several benefits. The most efficient design for a natural ventilation building should implement both types of ventilation.
Contents
Process
The static pressure of air is the pressure in a free-flowing air stream and is depicted by isobars in weather maps. Differences in static pressure arise from global and microclimate thermal phenomena and create the air flow we call wind. Dynamic pressure is the pressure exerted when the wind comes into contact with an object such as a hill or a building and it is related to the air density and the square of the wind speed. The impact of wind on a building affects the ventilation and infiltration rates through it and the associated heat losses or heat gains. Wind speed increases with height and is lower towards the ground due to frictional drag.
The impact of wind on the building form creates areas of positive pressure on the windward side of a building and negative pressure on the leeward and sides of the building. Thus building shape is crucial in creating the wind pressures that will drive air flow through its apertures. In practical terms wind pressure will vary considerably creating complex air flows and turbulence by its interaction with elements of the natural environment (trees, hills) and urban context (buildings, structures). Vernacular and traditional buildings in different climatic regions rely heavily on natural ventilation for maintaining thermal comfort conditions in the enclosed spaces.
Design
Typical building design relies on rules of thumb for harnessing the power of wind for the purpose of natural ventilation. Design guidelines are offered in building regulations and other related literature and include a variety of recommendations on many specific areas such as:
- Building location and orientation
- Building form and dimensions
- Window typologies and operation
- Other aperture types (doors, chimneys)
- Construction methods and detailing (infiltration)
- External elements (walls, screens)
- Urban planning conditions
The following design guidelines are selected from the Whole Building Design Guide, a program of the National Institute of Building Sciences[2] :
- Maximize wind-induced ventilation by siting the ridge of a building perpendicular to the summer winds
- Widths of naturally ventilated zone should be narrow (45' max)
- Each room should have two separate supply and exhaust openings. Locate exhaust high above inlet to maximize stack effect. Orient windows across the room and offset from each other to maximize mixing within the room while minimizing the obstructions to airflow within the room.
- Window openings should be operable by the occupants
- Consider the use of clerestories or vented skylights.
Wind driven ventilation
Wind driven ventilation or roof mounted ventilation design in buildings provides ventilation to occupants using the least amount of resources. Mechanical ventilation drawbacks include the use of equipment that is high in embodied energy and the consumption of energy during operation. By utilising the design of the building, Wind driven ventilation takes advantage of the natural passage of air without the need for high energy consuming equipment. Windcatchers are able to aid wind driven ventilation by directing air in and out of buildings.
Wind driven ventilation depends on wind behavior, on the interactions with the building envelope and on openings or other air exchange devices such as inlets or chimneys. For a simple volume with two openings, the cross wind flow rate was calculated by Aynsley et al.[3]
Q=Uwind√((Cp1-Cp2)/(1/A12C12)+(1/A22C22) (1)
The knowledge of the urban climatology i.e. the wind around the buildings is crucial when evaluating the air quality and thermal comfort inside buildings as air and heat exchange depends on the wind pressure on facades. As we can see in the equation (1), the air exchange depends linearly on the wind speed in the urban place where the architectural project will be built. CFD (Computational Fluid Dynamics) tools and zonal modelings are usually used to calculate pressure. One of these CFD tools, called UrbaWind (UrbaWind) makes the link between this pressure and the real urban climatology. It computes with a macroscopic method the mass flow rate incoming the building for each wind characteristic (incidence and velocity magnitude), to finally give cross ventilation statistics according to the wind statistics of the considered urban location. It helps quantifying the natural cross ventilation induced by the wind flow crossing the buildings.
Wind driven ventilation has several significant benefits:
- Greater magnitude and effectiveness
- Readily available (natural occurring force)
- Relatively economic implementation
- User friendly (when provisions for control are provided to occupants)
Some of the important limitations of wind driven ventilation:
- Unpredictability and difficulties in harnessing due to speed and direction variations
- The quality of air it introduces in buildings may be polluted for example due to proximity to an urban or industrial area
- May create a strong draught, discomfort.
Stack driven ventilation
-
- (For more details, see Stack effect)
Stack effect is temperature induced. When there is a temperature difference between two adjoining volumes of air the warmer air will have lower density and be more buoyant thus will rise above the cold air creating an upward air stream. Forced stack effect in a building takes place in a traditional fire place. Passive stack ventilators are common in most bathrooms and other type of spaces without direct access to the outdoors.
In order for a building to be ventilated adequately via stack effect the inside and outside temperatures must be different so that warmer indoor air rises and escapes the building at higher apertures, while colder, denser air from the exterior enters the building through lower level openings. Stack effect increases with greater temperature difference and increased height between the higher and lower apertures. The neutral plane in a building occurs at the location between the high and low openings at which the internal pressure will be the same as the external pressure (in the absence of wind). Above the neutral plane, the air pressure will be positive and air will rise. Below the neutral plane the air pressure will be negative and external air will be drawn into the space. Stack driven ventilation has several significant benefits:
- Does not rely on wind: can take place on still, hot summer days when it is most needed.
- Natural occurring force (hot air rises)
- Stable air flow (compared to wind)
- Greater control in choosing areas of air intake
- Sustainable method
Limitations of stack driven ventilation:
- Lower magnitude compared to wind ventilation
- Relies on temperature differences (inside/outside)
- Design restrictions (height, location of apertures) and may incur extra costs (ventilator stacks, taller spaces)
- The quality of air it introduces in buildings may be polluted for example due to proximity to an urban or industrial area
Natural ventilation in buildings relies mostly in wind pressure differences but stack effect can augment this type of ventilation and partly restore air flow rates during hot, still days. Stack ventilation can be implemented in ways that air inflow in the building does not rely solely on wind direction. In this respect it may provide improved air quality in some types of polluted environments such as cities. For example air can be drawn through the backside or courtyards of buildings avoiding the direct pollution and noise of the street facade. Wind can augment the stack effect but also reduce its effect depending on its speed, direction and the design of air inlets and outlets. Therefore prevailing winds must be taken into account when designing for stack effect ventilation.
Examples of stack effect ventilation can be seen on aluminium smelters, steel mills, and glass plants. Stack effect ventilators have undergone numerous evolutionary steps in recent years to correspond to new safety standards for protection against weather penetration, air hygiene for plant workforce and methodology of construction to reduce total installed costs of greenfield and brownfield projects.
Estimating stack effect ventilation
The natural ventilation flow rate can be estimated with this equation:[4]
- English units:
-
where: QS = Stack vent airflow rate, ft³/s A = cross-sectional area of opening, ft² (assumes equal area for inlet and outlet) Cd = Discharge coefficient for opening (typical value is 0,62) g = gravitational acceleration, around 32.2 ft/s² on Earth Hd = Height from midpoint of lower opening to neutral pressure level (NPL), ft NPL
= location/s in the building envelope with no pressure difference between inside and outside (ASHRAE 2001, p.26.11) TI = Average indoor temperature between the inlet and outlet, °R TO = Outdoor temperature, °R
- SI units:
-
where: QS = Stack vent airflow rate, m³/s A = cross-sectional area of opening, m² (assumes equal area for inlet and outlet) Cd = Discharge coefficient for opening (typical value is 0,62) g = gravitational acceleration, around 9.81 m/s² on Earth Hd = Height from midpoint of lower opening to neutral pressure level (NPL), m NPL
= location/s in the building envelope with no pressure difference between inside and outside (ASHRAE 2001, p.26.11) TI = Average indoor temperature between the inlet and outlet, K TO = Outdoor temperature, K
Assessing performance
One way to measure the performance of a naturally ventilated space is to measure the air movement across a space. In order for ventilation to be effective, there must be exchange between outdoor air and room air. A common method for measuring ventilation effectiveness is to use a tracer gas.[5] The first step is to close all windows, doors, and openings in the space. Then, a tracer gas is added to the air. The reference, American Society for Testing and Materials (ASTM) Standard E741: Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution, describes which tracer gases can be used for this kind of testing and provides information about the chemical properties, health impacts, and ease of detection.[6] Once the tracer gas has been added, mixing fans can be used to distribute the tracer gas as uniformly as possible throughout the space. To do a decay test, the concentration of the tracer gas is first measured when the concentration of the tracer gas is constant. Windows and doors are then opened and the concentration of the tracer gas in the space is measured at regular time intervals to determine the decay rate of the tracer gas. The airflow can be deduced by looking at the change in concentration of the tracer gas over time. For further details on this test method, refer to ASTM Standard E741.[6] For standards relating to ventilation rates, refer to ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality.[7] Another reference is ASHRAE Standard 62.2: Ventilation and Acceptable Indoor Air Quality in low-rise Residential Buildings.[8]
Thermal comfort
When designing ventilation systems, mechanical engineers refer to ASHRAE Standard 55: Thermal Environmental Conditions for Human Occupancy, which was first established in 1966.[9] Throughout its revisions, its scope has been consistent with its currently articulated purpose, “to specify the combinations of indoor thermal environmental factors and personal factors that will produce thermal environmental conditions acceptable to a majority of the occupants within the space.”[9] Until 2004, this standard was used to specify the same criteria for thermal comfort for naturally and mechanically ventilated systems. From 1995 to 1998, ASHRAE funded a project, ASHRAE RP-884: developing an adaptive model of thermal comfort and preference, to investigate whether or not there are differences in occupant thermal response in mechanically versus naturally ventilated buildings.[10] The ASHRAE RP-884 database included 21,000 sets of raw data from 160 different office buildings in diverse climates on 4 continents.[10] The results of this extensive field research indicated that there are differences between naturally ventilated and mechanically ventilated spaces with regards to occupant thermal response, change in clothing, availability of control, and shifts in occupant expectations.[9] In 2004, this led to a revision of the ASHRAE Standard 55 to include a new section, 5.3: Optional Method For Determining Acceptable Thermal Conditions in Naturally Ventilated Spaces, which specifies acceptable operative temperature ranges for naturally ventilated spaces.[9] As a result, the design of natural ventilation systems became more feasible, which was acknowledged by ASHRAE as a way to further sustainable, energy efficient, and occupant-friendly design.[9]
See also
- Ventilation (architecture)
- Infiltration (HVAC)
- Air-side economizers
- Solar chimney
- Windcatcher
- Indoor air quality
- Sick building syndrome
- Heating, Ventilation and Air-Conditioning
- Mechanical engineering
- Architectural engineering
- Green building
- Passive cooling
- Mixed Mode Ventilation
- Room air distribution
- Thermal comfort
- air conditioning
- ASHRAE
- Glossary of HVAC
References
- ^ Linden, P. F. (1999). "The Fluid Mechanics of Natural Ventilation". Annual Review of Fluid Mechanics 31: 201–238. doi:10.1146/annurev.fluid.31.1.201.
- ^ Walker, Andy. "Natural Ventilation". National Institute of Building Sciences. http://www.wbdg.org/resources/naturalventilation.php.
- ^ Aynsley, R.M.; W. Melbourn, B.J. Vickery (1977). Architectural Aerodynamics. London: Applied Science Publishers.
- ^ Hui, Sam. "Lecture: Air Movement and Natural Ventilation". Integrated Building Technology, Department of Architecture, University of Hong Kong. http://www.arch.hku.hk/teaching/lectures/airvent/sect03.htm.
- ^ McWilliams, Jennifer (2002). "Review of air flow measurement techniques. LBNL Paper LBNL-49747.". Lawrence Berkeley National Lab. http://escholarship.org/uc/item/7532b84f?query=Review%20of%20air%20flow%20measurement%20techniques.
- ^ a b ASTM Standard E741-11: Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution. West Conshohocken, PA: ASTM International. 2006.
- ^ ANSI/ASHRAE Standard 62.1: Ventilation for Acceptable Indoor Air Quality. Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers. 2010.
- ^ ANSI/ASHRAE Standard 62.2: Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings. Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers. 2010.
- ^ a b c d e ANSI/ASHRAE Standard 55: Thermal Environmental Conditions for Human Occupancy. Atlanta, GA: American Society of Heating, Refrigerating and Air-Conditioning Engineers. 2010.
- ^ a b de Dear, Richard J.; Gail S. Brager (2002). "Thermal Comfort in Naturally Ventilated Buildings: Revisions to ASHRAE Standard 55.". Energy and Buildings 34 (6). doi:10.1016/S0378-7788(02)00005-1.
External links
University-based research centers that currently conduct natural ventilation research:
- The Center for the Built Environment (CBE), University of California, Berkeley. http://www.cbe.berkeley.edu/
- Lawrence Berkeley National Laboratory, Berkeley, California. http://www.lbl.gov/
- Department of Architecture, Massachusetts Institute of Technology. http://architecture.mit.edu/building-technology/program/research-topics
- Faculty of Architecture, Design and Planning, University of Sydney, Australia. http://sydney.edu.au/architecture/research/research_archdessci.shtml
Natural Ventilation Guidelines:
- Whole Building Design Guide, National Institute of Building Sciences http://www.wbdg.org/resources/naturalventilation.php
- "Natural Ventilation for Infection Control in Health-Care Settings," a report (including design guidelines) by World Health Organization for naturally ventilated health-care facilities.http://whqlibdoc.who.int/publications/2009/9789241547857_eng.pdf
Categories:- Ventilation
- Heating, ventilating, and air conditioning
- Sustainable building
- Building engineering