Infiltration (HVAC)

Infiltration (HVAC)

Infiltration is the unintentional or accidential introduction of outside air into a building, typically through cracks in the building envelope and through use of doors for passage ["Fundamentals volume of the ASHRAE Handbook", Ch. 27, ASHRAE, Inc., 2005] . Infiltration is sometimes called air leakage. The leakage of room air out of a building, intentionally or not, is called exfiltration. Infiltration is caused by wind, building pressurization and by air buoyancy forces known commonly as the stack effect.

Infiltration measures

The infiltration rate is the volumetric flow rate of outside air into a building, typically in cubic feet per minute (CFMs) or liters per second (LPSs). The air exchange rate, ("I"), is the number of interior volume air changes that occur per hour, and has units of 1/h. The air exchange rate is also known as air changes per hour ("ACHs").

ACH can be calculated by multiplying the building's CFM by 60, and then dividing by the building volume. (CFM x 60)/volume

Infiltration as ventilation air

In many smaller buildings, 'forced' or 'mechanical' ventilation is not used to introduce ventilation air. Instead, natural ventilation, via operable windows and other openings, exhaust fans, and infiltration are used to provide ventilation air. Typically, at least one-third air change per hour is considered the minimum. Recently, ASHRAE Standard 62.2 has been adopted (2004); it clarifies the ventilation air requirements for low-rise residences. The Standard specifies when, for example, forced ventilation is required in houses.

Controlling infiltration

Because infiltration is uncontrolled, and admits unconditioned air, it is generally considered undesirable except for ventilation air purposes. Typically, infiltration is minimized to reduce dust, to increase thermal comfort, and to decrease energy consumption. For all buildings, infiltration can be reduced via sealing cracks in a building's envelope, and for new construction or major renovations, by installing continuous air retarders. In buildings where forced ventilation is provided, their HVAC designers typically choose to slightly pressurize the buildings by admiting more outside air than exhausting so that infiltration is drammatically reduced.

Energy savings

In typical modern U.S. residences, about one-third of the HVAC energy consumption is due to infiltration. Another third is to ground-contact, and the remainder is to heat losses and gains through windows, walls, and other thermal "loads". As such, reducing infiltration can yield significant energy savings, with rapid payback. In cold climates, with a 15 MPH wind, residences often have air exchange rates of 1.0 to 1.5 ACHs, far in excess of the ventilation air needs and are thus called "loose construction". While it is possible to build a house too "tightly", e.g., 0.25 ACH, it is very easy to reduce infiltration rates to less than 1.0 ACH. Smoke candles and blower-door tests can help identify less-than-obvious leaks. The Weatherization article describes methods for energy savings further.

See also

*Vapor barrier
*Ventilation (architecture)
*Natural ventilation
*Indoor air quality
*Thermal comfort
*Sick building syndrome
*Heating, Ventilation and Air-Conditioning
*Psychrometrics
*Mechanical engineering
*Architectural engineering
*Green building

References


Wikimedia Foundation. 2010.

Игры ⚽ Поможем сделать НИР

Look at other dictionaries:

  • Infiltration — may refer to:*Infiltration (HVAC), a heating, ventilation, and air conditioning (HVAC) term for air leakage into buildings *Infiltration (hydrology), downward movement of water through soil *Infiltration (medical), the diffusion or accumulation… …   Wikipedia

  • HVAC — may also stand for High voltage alternating current. See also: Glossary of HVAC HVAC systems use ventilation air ducts installed throughout a building that supply conditioned air to a room through rectangular or round outlet vents, called… …   Wikipedia

  • Natural ventilation — The ventilation system of a regular earthship. Natural ventilation is the process of supplying and removing air through an indoor space without using mechanical systems. It refers to the flow of external air to an indoor space as a result of wind …   Wikipedia

  • Indoor air quality — (IAQ) is a term referring to the air quality within and around buildings and structures, especially as it relates to the health and comfort of building occupants. IAQ can be affected by microbial contaminants (mold, bacteria), gases (including… …   Wikipedia

  • ASHRAE Handbook — The ASHRAE Handbook is the four volume flagship publication of the nonprofit technical organization American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. (ASHRAE). This Handbook is considered the practical repository of… …   Wikipedia

  • Ventilation (architecture) — Ventilation is the intentional movement of air from outside a building to the inside. It is the V in HVAC. With clothes dryers, and combustion equipment such as water heaters, boilers, fireplaces, and wood stoves, their exhausts are often called… …   Wikipedia

  • Curtain wall — For defensive curtain walls in medieval buildings, see Curtain wall (fortification). Glass curtain wall of the Bauhaus Dessau A curtain wall is an outer covering of a building in which the outer walls are non structural, but merely keep out the… …   Wikipedia

  • Passive solar building design — Elements of passive solar design, shown in a direct gain application …   Wikipedia

  • Vapor barrier — 6 mil Polyethylene plastic sheet as vapor barrier between insulation and gypsum board …   Wikipedia

  • Stack effect — is the movement of air into and out of buildings, chimneys, flue gas stacks, or other containers, and is driven by buoyancy. Buoyancy occurs due to a difference in indoor to outdoor air density resulting from temperature and moisture differences …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”