Circulator pump

Circulator pump

A circulator pump is a specific type of pump used to circulate gases, liquids, or slurries in a closed circuit. They are commonly found circulating water in a hydronic heating or cooling system. Because they only circulate liquid within a closed circuit, they only need to overcome the friction of a piping system (as opposed to lifting a fluid from a point of lower potential energy to a point of higher potential energy).

Circulator pumps as used in hydronic systems are usually electrically powered centrifugal pumps. As used in homes, they are often small, sealed, and rated at a fraction of a horsepower, but in commercial applications they range in size up to many horsepower and the electric motor is usually separated from the pump body by some form of mechanical coupling. The sealed units used in home applications often have the motor rotor, pump impeller, and support bearings combined and sealed within the water circuit. This avoids one of the principal challenges faced by the larger, two-part pumps: maintaining a water-tight seal at the point where the pump drive shaft enters the pump body.

Small- to medium-sized circulator pumps are usually supported entirely by the pipe flanges that join them to the rest of the hydronic plumbing. Large pumps are usually pad-mounted.

Pumps that are used solely for closed hydronic systems can be made with cast iron components as the water in the loop will either become de-oxygenated or be treated with chemicals to inhibit corrosion. But pumps that have a steady stream of oxygenated, potable water flowing through them must be made of more expensive materials such as bronze.

Use with domestic hot water

Bronze pumps are often used to circulate domestic hot water so that a faucet will provide hot water instantly upon demand. In regions where water conservation issues are rising in importance with rapidly expanding and urbanizing populations local water authorities offer rebates to homeowners and builders that install a circulator pump to save water. In typical one-way plumbing without a circulation pump, water is simply piped from the water heater through the pipes to the tap. Once the tap is shut off, the water remaining in the pipes cools producing the familiar wait for hot water the next time the tap is opened. By adding a circulator pump and constantly circulating a small amount of hot water through the pipes from the heater to the furthest fixture and back to the heater, the water in the pipes is always hot, and no water is wasted during the wait. The tradeoff is the energy wasted in operating the pump and the additional demand on the water heater to make up for the heat lost from the constantly-hot pipes. While the majority of these pumps mount nearest to the hot water heater and have no adjustable temperature capabilities, a significant reduction in energy can be achieved by utilizing a temperature adjustable thermostatically controlled circulation pump mounted at the last fixture on the loop. Thermostatically controlled circulation pumps allow owners to choose the desired temperature of hot water to be maintained within the hot water pipes since most homes do not require 120 °F (49 °C) degree water instantly out of their taps. Thermostatically controlled circulation pumps cycle on and off to maintain a user's chosen temperature and consume less energy than a continuously operating pump. By installing a thermostatically controlled pump just after the farthest fixture on the loop, cyclic pumping maintains ready hot water up to the last fixture on the loop instead of wasting energy heating the piping from the last fixture to the water heater. Often installing a circulation pump at the farthest fixture on hot water circulation loop due to limited available space, cosmetics, noise restrictions or lack of available power. Recent advancements in hot water circulation technology allow for benefiting from temperature controlled pumping without having to install the pump at the last fixture on the hot water loop. These advanced hot water circulation systems utilize a water contacting temperature probe strategically installed at the last fixture on the loop to minimize the energy wasted heating lengthy return pipes. Thermal insulation applied to the pipes helps mitigate this second loss and minimize the amount of water that must be pumped to keep hot water constantly available.

The traditional hot water recirculation system uses a dedicated return line from the point of use located farthest from the hot water tank back to the hot water tank. In homes where this return line was not installed the cold water line is used as a return line. The first of two system types has a pump mounted at the hot water heater while a "normally-open" thermostatic control valve gets installed at the furthest fixture from the water heater and closes once hot water contacts the valve to control crossover flow between the hot and cold lines. A second type of system utilizes a thermostatically controlled pump which gets installed at the furthest fixture from the water heater. These thermostatically controlled pumps often have a built-in "normally closed" check-valve which prevents water in the cold water line from entering into the hot water line. Compared to a dedicated return line, using the cold water line as a return has the disadvantage of heating the cold water pipe (and the contained water). Accurate temperature monitoring and active flow control can minimize loss of cold water within the cold water line. Technological advancements within the industry allowed for incorporating timers to limit the operations during specific hours of the day to reduce energy waste by only operating when occupants where likely to use hot water. Additional advancements in technology include pumps which cycle on and off to maintain hot water temperature versus a continuously operating pump which consumes more electrical energy. Reduced energy waste and discomfort is possible by preventing occurrences of hot water line siphoning in open-loop hot water circulation systems which utilize the cold water line to return water back to the water heater. Hot Water Line Siphoning occurs when water from within the hot water line siphons or is forced into the cold water line due to differences in water pressure between the hot and cold water lines. Utilizing "normally closed" solenoid valve significantly reduces energy consumption by preventing siphoning of non-hot water out of hot water lines during cold water use. Using cold water instantly lowers the water pressure in the cold water lines, the higher water pressure in the hot water lines force water through "normally open" thermostatic crossover valves and backflow check valves (which only prevent cold water from flowing into hot water line), increasing the energy demand on the water heater.

Circulator Pump Optimizing

In the past circulating pumps operated continuously 24 hours a day or utilized a timer to schedule operating times around anticipated hot water demand periods. In a residential environment where occupant's lifestyles are anything but routine, using a 24-hour timer to schedule circulator pump operations would not be practical. Growing environmental concerns call for greener eco-friendly products capable of satisfying consumers with different lifestyles. Adapting intelligent circulating pump control to an existing system instantly adds greener control capabilities like; cycle on and off based on a temperature set point (fixed/adjustable) or time-of-day or day-of-week or push-button on-demand or occupancy sensor or sound sensor and more. Minimizing circulator pump operations saves valuable resources and the environment.

See also


Wikimedia Foundation. 2010.

Игры ⚽ Нужно решить контрольную?

Look at other dictionaries:

  • Circulator (disambiguation) — Circulator may refer to: Optical circulator Circulator pump DC Circulator often referred to as the Circulator Downtown circulator This disambiguation page lists articles associated with the same title. If an …   Wikipedia

  • Pump — For information on Wikipedia project related discussions, see . A pump is a device used to move gases, liquids or slurries. A pump moves liquids or gases from lower pressure to higher pressure, and overcomes this difference in pressure by adding… …   Wikipedia

  • Zone valve — A zone valve is a specific type of valve used to control the flow of water or steam in a hydronic heating or cooling system.In the interest of improving efficiency and occupant comfort, such systems are commonly divided up into multiple zones.… …   Wikipedia

  • Thermostat — This article is about the temperature regulating device. For the French cooking oven temperature scale, see Gas Mark#Other cooking temperature scales. Honeywell s iconic The Round model T87 thermostat, one of which is in the Smithsonian …   Wikipedia

  • Hydronics — is the name for the use of water as the heat transfer medium in heating and cooling systems. Some of the oldest and most common examples are steam and hot water radiators. In large scale commercial buildings such as high rise and campus… …   Wikipedia

  • Grundfos — is the world s largest pump manufacturer, based in Denmark (Scandinavia) with more than 18,000 employees globally. The leading pump manufacturers in the world, with an annual production of more than 12 million pump units, Circulator pumps (UP),… …   Wikipedia

  • Vector soliton — Among all the soliton considered, the optical soliton draws the most attention as it is possible to generate ultrafast pulses and has wider application. optical soliton can be classified as two groups:temporal soliton and spatial soliton.however …   Wikipedia

  • Forced-air — A Forced air or Warm air heating system is one which uses air as its heat transfer medium. These systems use ductwork and vents as a means of air distribution. The return plenum carries the air from several large return grills (vents) to a… …   Wikipedia

  • Water heating — is a thermodynamic process using an energy source to heat water above its initial temperature. Typical domestic uses of hot water are for cooking, cleaning, bathing, and space heating. In industry, both hot water and water heated to steam have… …   Wikipedia

  • Washington, D.C. — This article is about the place. For the novel, see Washington, D.C. (novel). Washington, D.C.   Federal district   …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”