Multipoint ground

Multipoint ground

A Multipoint Ground is an alternate type of electrical installation that attempts to solve the Ground Loop and Mains hum problem by creating many alternate paths for electrical energy to find its way back to ground. The distinguishing characteristic of a multipoint ground is the use of many interconnected grounding conductors into a loose grid configuration. There will be many paths between any two points in a multipoint grounding system, rather than the single path found in a star topology ground. This type of ground may also be known as a Signal Reference Grid or Ground (SRG) or an Equipotential Ground.

Contents

Advantages

If installed correctly, it can maintain reference ground potential much better than a star topology in a similar application across a wider range of frequencies and currents.

Disadvantages

  • More complicated to install and maintain over the long term, and can be more expensive to install.

Star topology systems can be converted to multipoint systems by installing new conductors between old existing ones. However, this should be done with care as it can inadvertently introduce noise onto signal lines during the conversion process. The noise can be diminished over time as noisy and failed components are removed and repaired, but some isolation of high current (e.g. motors and lighting) and sensitive low current (e.g. amplifiers and radios) equipment may always be necessary.

Design Considerations

A multipoint grounding system can solve several problems, but they must all be addressed in turn. The size of the conductors must be designed to meet the expected load in operations and in lightning protection. The amount of cross bonding, and the topology of the grids, is determined by the expected frequencies in the signals to be carried and the uses the installation will be put to.

A ground grid is provided primarily for safety, and the size of the conductors is probably governed by local building or electrical code. One factor to keep in mind is that since the final grid will have multiple paths to ground, the final system resistance to ground will likely be lower than for a typical star ground. But this does not change the need for adequate conductor size to any given piece of equipment in case of a fault.

Lightning protection is provided by bonding the multipoint ground grid to one or more grounding rods under or at the perimeter of the building, and then up to the lightning rods. If the building has significant metal framing elements, these should be bonded to the lightning rods and grounding rods as well.

If the building has large motors, driving such things as fans, pumps, elevators, etc., these should also be on the multipoint grid. However, they should not be on segments of the grid that will service equipment such as audio amplifiers, small signal radio circuits, computer networks, sensitive electrical instrumentation, etc. Since building two grids into the same building may be prohibitively expensive, a good compromise is to connect the low frequency, high current equipment to the grid at or near the ground rods and entrance transformers, in such a way that their load will not flow across the segment of the grid connected to the low current equipment. Thus the system is still an electrically continuous unit, but motor noise does not impinge directly into signal paths.

The cross bonding is governed by the frequencies and wavelengths to be protected against. A multipoint ground is at its best when it allows currents of many different frequencies to find a path to ground. If the system is expected to always have no more than main current present, the wavelengths involved at 50 or 60 Hz will cause the system design to become a star topology. But if higher frequencies are present, they need to be closer. In general, the spacing between nodes should be less than 1/8 of the shortest wavelength present. This will guarantee that current can always flow no matter which path it tries to take. If less than 1/8 wavelength node spacing cannot be achieved, then at least include as many cross connects as possible, as closely spaced as possible.

External links

GROUNDING, BONDING & SHIELDING FOR ELECTRONIC EQUIPMENTS & FACILITIES, VOLUME 1 & 2,

GROUNDING, BONDING AND SHIELDING FOR COMMON LONG HAUL/TACTICAL COMMUNICATION SYSTEMS INCLUDING GROUND BASED COMMUNICATIONS-ELECTRONICS FACILITIES AND EQUIPMENTS


Wikimedia Foundation. 2010.

Игры ⚽ Поможем написать курсовую

Look at other dictionaries:

  • Multipoint — may refer to: Multi point fuel injection, an injection scheme for metering fuel into an internal combustion engine Multipoint ground, a type of electrical installation which involves the creation of many alternate paths for electrical energy to… …   Wikipedia

  • Digital radio — has several meanings: 1. Today the most common meaning is digital radio broadcasting technologies, such as the digital audio broadcasting (DAB) system, also known as Eureka 147. In these systems, the analog audio signal is digitized into zeros… …   Wikipedia

  • Satellite television — List of digital television broadcast standards DVB standards (Europe) DVB S (satellite) DVB S2 DVB T (terrestrial) DVB T2 DVB C …   Wikipedia

  • Aerial refueling — A C 17 Globemaster refuels through the boom of a Boeing KC 135 Stratotanker …   Wikipedia

  • WiMAX — Worldwide Interoperability for Microwave Access Logo trademarked by the WiMAX Forum …   Wikipedia

  • Low-voltage differential signaling — Low voltage differential signaling, or LVDS, is an electrical signaling system that can run at very high speeds over inexpensive twisted pair copper cables. It was introduced in 1994, and has since become very popular in computers, where it forms …   Wikipedia

  • Diamond tool — A close up of the segment of a diamond saw blade A diamond tool is a cutting tool with diamond grains fixed on the functional parts of the tool via a bonding material or another method.[1] As diamond is a superhard material, diamond tools have… …   Wikipedia

  • EIA-485 — In telecommunications, EIA 485 (formerly RS 485 or RS485) is an electrical specification of a two wire, [ [http://www.chipkin.com/articles/rs485 cables why you need 3 wires for 2 two wire rs485 Why you need 3 wires for 2 (two) wire RS485] ] half… …   Wikipedia

  • ECHELON — is a name used in global media and in popular culture to describe a signals intelligence (SIGINT) collection and analysis network operated on behalf of the five signatory states to the UK USA Security Agreement (Australia, Canada, New Zealand,… …   Wikipedia

  • Computers and Information Systems — ▪ 2009 Introduction Smartphone: The New Computer.       The market for the smartphone in reality a handheld computer for Web browsing, e mail, music, and video that was integrated with a cellular telephone continued to grow in 2008. According to… …   Universalium

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”