Contactor

Contactor
AC contactor for pump application.
In semiconductor testing, contactor can also refer to the specialised socket that connects the device under test.
In process industries a contactor is a vessel where two streams interact, for example, air and liquid.

A contactor is an electrically controlled switch used for switching a power circuit, similar to a relay except with higher current ratings.[1] A contactor is controlled by a circuit which has a much lower power level than the switched circuit.

Contactors come in many forms with varying capacities and features. Unlike a circuit breaker, a contactor is not intended to interrupt a short circuit current. Contactors range from those having a breaking current of several amperes and 24 V DC to thousands of amperes and many kilovolts. The physical size of contactors ranges from a device small enough to pick up with one hand, to large devices approximately a meter (yard) on a side.

Contactors are used to control electric motors, lighting, heating, capacitor banks, and other electrical loads.

Contents

Construction

Albright SPST DC contactor,
sometimes used in EV conversions
Powerful DC contactor with electro-pneumatic drive

A contactor has three components. The contacts are the current carrying part of the contactor. This includes power contacts, auxiliary contacts, and contact springs. The electromagnet provides the driving force to close the contacts. The enclosure is a frame housing the contact and the electromagnet. Enclosures are made of insulating materials like Bakelite, Nylon 6, and thermosetting plastics to protect and insulate the contacts and to provide some measure of protection against personnel touching the contacts. Open-frame contactors may have a further enclosure to protect against dust, oil, explosion hazards and weather.

Magnetic blowouts use blowout coils to lengthen and move the electric arc. These are especially useful in DC power circuits. AC arcs have periods of low current, during which the arc can be extinguished with relative ease, but DC arcs have continuous high current, so blowing them out requires the arc to be stretched further than an AC arc of the same current. The magnetic blowouts in the pictured Albright contactor (which is designed for DC currents) more than double the current it can break, increasing it from 600 A to 1,500 A.

Sometimes an economizer circuit is also installed to reduce the power required to keep a contactor closed; an auxiliary contact reduces coil current after the contactor closes. A somewhat greater amount of power is required to initially close a contactor than is required to keep it closed. Such a circuit can save a substantial amount of power and allow the energized coil to stay cooler. Economizer circuits are nearly always applied on direct-current contactor coils and on large alternating current contactor coils.

A basic contactor will have a coil input (which may be driven by either an AC or DC supply depending on the contactor design). The coil may be energized at the same voltage as the motor, or may be separately controlled with a lower coil voltage better suited to control by programmable controllers and lower-voltage pilot devices. Certain contactors have series coils connected in the motor circuit; these are used, for example, for automatic acceleration control, where the next stage of resistance is not cut out until the motor current has dropped.[2]

Operating principle

Unlike general-purpose relays, contactors are designed to be directly connected to high-current load devices. Relays tend to be of lower capacity and are usually designed for both normally closed and normally open applications. Devices switching more than 15 amperes or in circuits rated more than a few kilowatts are usually called contactors. Apart from optional auxiliary low current contacts, contactors are almost exclusively fitted with normally open contacts. Unlike relays, contactors are designed with features to control and suppress the arc produced when interrupting heavy motor currents.

When current passes through the electromagnet, a magnetic field is produced, which attracts the moving core of the contactor. The electromagnet coil draws more current initially, until its inductance increases when the metal core enters the coil. The moving contact is propelled by the moving core; the force developed by the electromagnet holds the moving and fixed contacts together. When the contactor coil is de-energized, gravity or a spring returns the electromagnet core to its initial position and opens the contacts.

For contactors energized with alternating current, a small part of the core is surrounded with a shading coil, which slightly delays the magnetic flux in the core. The effect is to average out the alternating pull of the magnetic field and so prevent the core from buzzing at twice line frequency.

Most motor control contactors at low voltages (600 volts and less) are air break contactors; air at atmospheric pressure surrounds the contacts and extinguishes the arc when interrupting the circuit. Modern medium-voltage motor controllers use vacuum contactors. High voltage contactors (greater than 1000 volts) may use vacuum or an inert gas around the contacts. High-voltage electric locomotives may be isolated from their overhead supply by roof-mounted circuit breakers actuated by compressed air; the same air supply may be used to "blow out" any arc that forms.[3][4]

Ratings

Contactors are rated by designed load current per contact (pole),[5] maximum fault withstand current, duty cycle, voltage, and coil voltage. A general purpose motor control contactor may be suitable for heavy starting duty on large motors; so-called "definite purpose" contactors are carefully adapted to such applications as air-conditioning compressor motor starting. North American and European ratings for contactors follow different philosophies, with North American general purpose machine tool contactors generally emphasizing simplicity of application while definite purpose and European rating philosophy emphasizes design for the intended life cycle of the application.

IEC

The current rating of the contactor depends on utilization category. For example IEC categories are described as:

  • AC1 - Non-inductive or slightly inductive loads
  • AC2 - Starting of slip-ring motors
  • AC3 - Starting of squirrel-cage motors and switching off only after the motor is up to speed. (Make Locked Rotor Amps (LRA), Break Full Load Amps (FLA))
  • AC4 - Starting of squirrel-cage motors with inching and plugging duty. Rapid Start/Stop. (Make and Break LRA)
  • AC11 - Auxiliary (control) circuits

NEMA

The current rating of smaller NEMA contactors or their auxiliaries are defined by NEMA ICS 5: Industrial Control and Systems, Control Circuit and Pilot Devices standard.[6] The nomenclature is a letter followed by a three digit number, the letter designates the current rating of the contacts and the current type (i.e., AC or DC) and the number designates the maximum voltage design values.[7] Some examples are listed below:

  • A150
  • A300
  • A600

Applications

Lighting control

Contactors are often used to provide central control of large lighting installations, such as an office building or retail building. To reduce power consumption in the contactor coils, latching contactors are used, which have two operating coils. One coil, momentarily energized, closes the power circuit contacts, which are then mechanically held closed; the second coil opens the contacts.

Magnetic starter

A magnetic starter is a device designed to provide power to electric motors. It includes a contactor as an essential component, while also providing power-cutoff and overload protection.

References

  1. ^ Terrell Croft and Wilford Summers (ed), American Electricans' Handbook, Eleventh Edition, McGraw Hill, New York (1987) ISBN 0-07013932-6 page 7-124
  2. ^ Croft, page 7-125
  3. ^ Hammond, Rolt (1968). "Development of electric traction". Modern Methods of Railway Operation. London: Frederick Muller. pp. 71–73. OCLC 467723. 
  4. ^ Ransome-Wallis, Patrick (1959). "Electric motive power". Illustrated Encyclopedia of World Railway Locomotives. London: Hutchinson. p. 173. ISBN 0486412474. OCLC 2683266. 
  5. ^ All about circuits
  6. ^ http://www.nema.org/engineering/icsstandards.html
  7. ^ http://www.moellercatalog.com/Documents/Chapter_14/14016_17.pdf

Wikimedia Foundation. 2010.

Игры ⚽ Поможем решить контрольную работу

Look at other dictionaries:

  • contactor — CONTACTÓR, contactoare, s.n. Întrerupător care închide un circuit sub acţiunea unei comenzi de la distanţă, menţinându l închis numai atâta timp cât se exercită această comandă. – Din fr. contacteur. Trimis de RACAI, 30.09.2003. Sursa: DEX 98 … …   Dicționar Român

  • contactor — [kän′tak΄tər, kän tak′tər] n. Elec. a heavy duty switching device, esp. a relay, used to open and close a circuit …   English World dictionary

  • Contactor — Este artículo o sección necesita referencias que aparezcan en una publicación acreditada, como revistas especializadas, monografías, prensa diaria o páginas de Internet fidedignas. Puedes añadirlas así o avisar …   Wikipedia Español

  • contactor — kontaktorius statusas T sritis automatika atitikmenys: angl. contact device; contactor vok. Kontaktgeber, m; Kontaktvorrichtung, f; Schütz, n rus. контактор, m pranc. contacteur, m …   Automatikos terminų žodynas

  • contactor — /kon tak teuhr, keuhn tak teuhr/, n. Elect. a mechanically operated switch for continuously establishing and interrupting an electric power circuit. [1905 10; CONTACT + OR2] * * * …   Universalium

  • contactor — noun /ˈkɑntæktɚ,ˈkɒntæktə/ A relay used to control an electrical power circuit …   Wiktionary

  • contactor — ► masculino ELECTROMAGNETISMO Interruptor automático a distancia basado en procedimientos electromagnéticos …   Enciclopedia Universal

  • contactor — con·tac·tor || kÉ’ntæktÉ™ n. mechanically operated switch for connecting and stopping an electric circuit; person who couples railroad cars (Archaic) …   English contemporary dictionary

  • contactor — con·tac·tor …   English syllables

  • contactor — con•tac•tor [[t]ˈkɒn tæk tər, kənˈtæk tər[/t]] n. elm a switch for continuously establishing and interrupting an electric power circuit • Etymology: 1905–10 …   From formal English to slang

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”