Manual fire alarm activation is done by using a pull station or call point.

Contents

Fire alarm pull station

A fire alarm pull station is an active fire protection device, usually wall-mounted, that, when activated, initiates an alarm on a fire alarm system. In its simplest form, the user activates the alarm by pulling the handle down, which completes a circuit and locks the handle in the activated position, sending an alarm to the fire alarm control panel. After operation, some fire alarm pull stations must be restored to the ready position using a special tool or key in order to deactivate the alarm sequence and return the system to normal. Primitive manual stations requiring only a single action or hand motion to activate, can be subject to unwanted activation by jarring or accidental contact. Early strategies to cope with this problem included requiring the operator to break a pane of glass to release an internal spring operated mechanism. Manual pull stations that require two hand motions such as; lift up and pull down or push in and pull down have since replaced the break glass and single action models in many modern installations.

Coded pull stations

In the past, pull stations controlled the entire system. These coded pull stations were much bigger than modern pulls and had a code wheel in them. This was a gear mechanism that was wound up when the station was pulled (and, unlike modern pull stations, the handle did not stay down). The gears would turn a small wheel with a specific number of teeth, which determined the coding. The teeth would push up on a contact, which would open and close a circuit, pulsing the code to the bells or horns. This code was used by building security to determine where the alarm was originating from. Example: a pull station in the fourth floor elevator lobby of an office building has a code of 5-3-1. When the station is pulled, the security officers in the building look up 5-3-1 in a master list of codes. After finding the location of the pull, they check to see if there is a real fire. If there is, they evacuate the building and call the fire department.

Antique Holtzer-Cabot coded pull station.

System tests could be conducted in one of two ways: In a coded pull station, there is either a test hole on the front (which is usually activated with an allen wrench) or a test switch on the inside. Turning the switch one way causes the notification appliances to sound continuously (or in the case of single-stroke bells, ding once). Turning it the other way and then activating the pull allows a silent test to be done in which the station's mechanical parts are checked to ensure proper function. Once pulled, the station would do at least four rounds of code before resetting itself. Coded pulls were typically used in new fire alarm systems until roughly the 1950s, and then occasionally up until the 1970s. Up until the late 1980s and early 1990s, some panels were made with an extra zone to accommodate any existing coded pull stations. Nowadays, coded pull stations are very rare and almost never seen in working fire alarm systems.

Modern pull stations

Many modern fire alarm pull stations are single action and only require the user to pull down the handle. Other fire alarm pull stations are dual-action, and as such require the user to perform a second task before pulling down, such as lifting up or pushing in a panel on the station or shattering a glass panel with an attached hammer. Perhaps the most recognizable pull station is the T-bar style pull. The style is so named because the handle is shaped like the letter "T". This style is manufactured by many companies.

Resetting a fire alarm pull station after it has been operated normally requires building personnel or emergency responders to open the station using a key, which often is either a hex key or a more traditional key. Opening the station normally causes the handle to go back to its original position, allowing the alarm to be reset from the fire alarm control panel after the station has been closed.

Activated pull station underneath a Stopper cover

In areas where false calls are a problem, pull stations may be covered with a clear plastic cover that sounds a loud tamper alarm when removed, creating focus on the fire alarm. If this is not a sufficient deterrent, the pull handle may be treated with ink, powder, or gel dye which can be used to help identify who pulled the alarm.[1]

Manual call points

In Europe, Australia, New Zealand, and Asia, pull stations are generally not used; instead a manual call point is used, which is usually referred to as an MCP within the fire protection industry, as a "transmitter" in Japan, or as a "break glass" by the UK public. They are used to allow building occupants to signal that a fire or other emergency exists within the building. They are usually connected to a central fire alarm panel which is in turn connected to an alarm system in the building, and often to a local fire brigade dispatcher as well. The first modern MCP arrived in Europe in 1972 and was developed by KAC.[2]

MCPs would historically be printed with FIRE as a title above a glass element, where the element would be glass which would be covered with plastic. This element design would be the old British Standard. The new European Standard, EN 54, says that the title should be the House Flame symbol, and the glass would appear differently. The glass will still be covered with plastic on the printed side.

Previously, the old British standard did not allow hinged covers and plastic resettable elements. Plastic elements must have the same printing as the EN54 glass.

See also

References

  1. ^ "Tamper Dye". Safety Media Incorporated. http://safetymedia.com/detail.aspx?ID=302. Retrieved 2011-04-17. 
  2. ^ "KAC Home Page". Kac.co.uk. http://www.kac.co.uk/final/home.htm. Retrieved 2009-07-16. 

External links


Wikimedia Foundation. 2010.

Игры ⚽ Поможем написать курсовую

Look at other dictionaries:

  • Fire sprinkler system — A fire sprinkler system is an active fire protection measure, consisting of a water supply, providing adequate pressure and flowrate to a water distribution piping system, onto which fire sprinklers are connected. Although historically only used… …   Wikipedia

  • Passive fire protection — (PFP) is an integral component of the three components of structural fire protection and fire safety in a building. PFP attempts to contain fires or slow the spread, through use of fire resistant walls, floors, and doors (amongst other examples) …   Wikipedia

  • Glossary of firefighting equipment — Note: This list is incomplete. You can help Wikipedia by [http://en.wikipedia.org/w/index.php?title=Glossary of firefighting equipment action=edit adding to it] . 0 9 * 1 3/4 inch hose: see attack hose * 2 1/2 inch hose: see attack hose , supply… …   Wikipedia

  • Heat detector — A heat detector is a device that responds to changes in ambient temperature. Typically, if the ambient temperature rises above a predetermined threshold an alarm signal is triggered. In the case of sprinkler systems, water will be released to… …   Wikipedia

  • Smoke detector — A smoke detector is a device that detects smoke, typically as an indicator of fire. Commercial, industrial, and mass residential devices issue a signal to a fire alarm system, while household detectors, known as smoke alarms, generally issue a… …   Wikipedia

  • Chernobyl disaster — This article is about the 1986 nuclear plant accident in Ukraine. For other uses, see Chernobyl (disambiguation). Chernobyl disaster …   Wikipedia

  • Emergency brake (train) — This article is about emergency brakes on trains. For emergency brakes in cars, see hand brake. Driver s brake handle in a UK Electric Multiple Unit On trains, the expression emergency brake has several meanings: The maximum brake force available …   Wikipedia

  • List of experiments from Lilo & Stitch — Kixx redirects here. For the soccer team, see Philadelphia Kixx. Image of experiment 626, also known as Stitch. The most popular of the experiments. This is a list of experiments from the Disney animated Lilo Stitch franchise, a series of… …   Wikipedia

  • Megas (character) — Megas is the main giant robot in the Cartoon Network animated television series Megas XLR . The name Megas stands for Mechanized Earth Guard Attack System.OriginIn the future, a war is taking place between humans and an alien race called the… …   Wikipedia

  • Nuclear warfare — Nuclear War redirects here. For other uses, see Nuclear War (disambiguation). Warfare Military history Eras Prehistoric Ancie …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”