Ampacity

Ampacity

Ampacity is the maximum amount of electrical current a conductor or device can carry before sustaining immediate or progressive deterioration. Also described as current rating or current-carrying capacity, ampacity is the RMS electric current which a device can continuously carry while remaining within its temperature rating. The ampacity of a cable depends on:

  • its insulation temperature rating;
  • the electrical resistance of the cable material;
  • frequency of the current, in the case of alternating current;
  • ability to dissipate heat, which depends on cable geometry and its surroundings;
  • ambient temperature.

All electrical conductors have some resistance to the flow of electricity, and electric current flowing through them causes voltage drop and power dissipation, which heats the cable. Copper or aluminum can conduct a large amount of current before melting, but long before the conductors melt, their insulation would be damaged by the heat.

The ampacity for a power cable is thus based on physical and electrical properties of the material & construction of the conductor and of its insulation, ambient temperature, and environmental conditions adjacent to the cable. Having a large overall surface area may dissipate heat well if the environment can absorb the heat.

In a long run of cable, different conditions govern, and installation regulations normally specify that the most severe condition along the run will govern the cable's rating. Cables run in wet or oily locations may carry a lower temperature rating than in a dry installation. Derating is necessary for multiple circuits in close proximity. When multiple cables are near, each contributes heat to the others and diminishes the amount of cooling air that can flow past the individual cables. The overall ampacity of the insulated conductors in a bundle of more than 3 must be derated, whether in a raceway or cable. Usually the derating factor is tabulated in a nation's wiring regulations.

Depending on the type of insulating material, common maximum allowable temperatures at the surface of the conductor are 60, 75, and 90 °C, often with an ambient air temperature of 30 °C. In the United States, 105 °C is allowed with ambient of 40 °C, for larger power cables, especially those operating at more than 2 kV. Likewise, specific insulations are rated 150, 200, or 250 °C.

The allowed current in cables generally needs to be decreased (derated) when the cable is covered with fireproofing material. For example, the United States National Electric Code, Table 310-16, specifies that up to three 8 AWG copper wires having a common insulating material (THWN) in a raceway, cable, or direct burial has an ampacity of 50 A when the ambient air is 30°C, the conductor surface temperature allowed to be 75°C. A single insulated conductor in air has 70 A rating.

Ampacity rating is normally for continuous current, and short periods of overcurrent occur without harm in most cabling systems. The acceptable magnitude and duration of overcurrent is a more complex topic than ampacity.

When designing an electrical system, one will normally need to know the current rating for the following:

Some devices are limited by power rating, and when this power rating occurs below their current limit, it is not necessary to know the current limit to design a system. A common example of this is lightbulb holders.

Current rating

For electronic components (such as transistors, voltage regulators, and the like), the term current rating is more-commonly used than ampacity, but the considerations are broadly similar. However the tolerance of short-term overcurrent is near zero for semiconductor devices, as their thermal capacities are extremely small.

See also

External links


Wikimedia Foundation. 2010.

Игры ⚽ Нужно решить контрольную?

Look at other dictionaries:

  • ampacity — noun The root mean square of the electrical current which a device (usually a wire) can carry within a specific environment (including temperature rating, power loss, heat dissipation, etc.) It is measured in amperes, (amps) and is most often… …   Wiktionary

  • длительный допустимый ток — (длительный) допустимый ток Максимальное значение электрического тока, который может протекать длительно по проводнику, устройству или аппарату при определенных условиях без превышения определенного значения их температуры в установившемся режиме …   Справочник технического переводчика

  • Circuit integrity — fireproofing of cable trays in Lingen/Ems, Germany using calcium silicate board system qualified to DIN 4102 …   Wikipedia

  • Neher–McGrath — The Neher–McGrath calculations calculate underground cable temperatures or maximum current ratings. From the basic principles that electric current leads to thermal heating and thermal power transfer to the ambient environment requires some… …   Wikipedia

  • ГОСТ Р МЭК 60050-826-2009: Установки электрические. Термины и определения — Терминология ГОСТ Р МЭК 60050 826 2009: Установки электрические. Термины и определения оригинал документа: ( длительный ) допустимый ток ((continuous) current carrying capacity ampacity (US)): Максимальное значение электрического тока, который… …   Словарь-справочник терминов нормативно-технической документации

  • Electrical conductor — Overhead conductors carry electric power from generating stations to customers. In physics and electrical engineering, a conductor is a material which contains movable electric charges. In metallic conductors such as copper or aluminum, the… …   Wikipedia

  • Electrical wiring — in general refers to insulated conductors used to carry electricity, and associated devices. This article describes general aspects of electrical wiring as used to provide power in buildings and structures, commonly referred to as building wiring …   Wikipedia

  • Knob and tube wiring — (sometimes abbreviated K T) was an early standardized method of electrical wiring in buildings, in common use in North America from about 1880 to the 1930s. [Terrell Croft and Wilford Summers (ed), American Electricans Handbook, Eleventh Edition …   Wikipedia

  • Cable tray — A cable tray system, according to the US National Electrical Code, is a unit or assembly of units or sections and associated fittings forming a rigid structural system used to securely fasten or support cables and raceways. Cable trays are used… …   Wikipedia

  • Mineral-insulated copper-clad cable — MIMS redirects here. For multi isotope imaging mass spectrometry, see Isotope mass spectrometry. PVC sheathed MICC cable. Conductor cross section area is 1.5 mm²; overall diameter is 7.2 mm …   Wikipedia