Earthing system

Earthing system

In sulvent systems, an earthing system defines the electrical potential of the conductors relative to that of the Earth's conductive surface. The choice of earthing system has implications for the safety and electromagnetic compatibility of the power supply. Note that regulations for earthing (grounding) systems vary considerably between different countries.

A "protective earth" (PE) connection ensures that all exposed conductive surfaces are at the same electrical potential as the surface of the Earth, to avoid the risk of electrical shock if a person touches a device in which an insulation fault has occurred. It ensures that in the case of an insulation fault (a "short circuit"), a very high current flows, which will trigger an overcurrent protection device (fuse, circuit breaker) that disconnects the power supply.

A "functional earth" connection serves a purpose other than providing protection against electrical shock. In contrast to a protective earth connection, a functional earth connection may carry a current during the normal operation of a device. Functional earth connections may be required by devices such as surge suppression and electromagnetic-compatibility filters, some types of antennas and various measurement instruments. Generally the protective earth is also used as a functional earth, though this requires care in some situations.

In household wiring

There are two main approaches to the problem of how to disconnect power when a live wire comes into contact with metalwork attached to the earthing system: One way is to get the resistance through the fault path and back to the supply very low by having a metallic connection from the earth back to the supply transformer (a TN system). Then when a fault happens a very high current will flow rapidly blowing a fuse (or tripping a circuit breaker).

The second approach, where such a direct connection is not used (a TT system), the resistance of the fault path back to the supply is too high for the branch circuit overcurrent protection to operate (blow a fuse or trip a circuit breaker). In such case a residual current detector is installed to detect the current leaking to ground and interrupt the circuit.

IEC terminology

International standard IEC 60364 distinguishes three families of earthing arrangements, using the two-letter codes TN, TT, and IT.

The first letter indicates the connection between earth and the power-supply equipment (generator or transformer):

It is possible to have both TN-S and TN-C-S supplies from the same transformer. For example, the sheaths on some underground cables corrode and stop providing good earth connections, and so homes where "bad earths" are found get converted to TN-C-S.

TT network

In a TT earthing system, the protective earth connection of the consumer is provided by a local connection to earth, independent of any earth connection at the generator.

IT network

In an IT network, the distribution system has no connection to earth at all, or it has only a high impedance connection. In such systems, an insulation monitoring device is used to monitor the impedance.

Other terminologies

While the national wiring regulations for buildings of many countries follow the IEC 60364 terminology, this is not currently the case in North America. In the United States, for example, the term ground is used instead of "earth".

Properties

Cost

* TN networks save the cost of a low-impedance earth connection at the site of each consumer. Such a connection (a buried metal structure) is required to provide "protective earth" in IT and TT systems.

* TN-C networks save the cost of an additional conductor needed for separate N and PE connections. However, to mitigate the risk of broken neutrals, special cable types and lots of connections to earth are needed.

* TT networks require RCD protection, and often an expensive time-delay type is needed to provide discrimination with an RCD downstream.

afety

* In TN, an insulation fault is very likely to lead to a high short-circuit current that will trigger an overcurrent circuit-breaker or fuse and disconnect the L conductors. With TT systems, the earth fault loop impedance can be too high to do this, or too high to do it quickly, so an RCD (or formerly ELCB) is usually employed. The provision of RCD or ELCB to ensure safe disconnection makes these installations EEBAD (Earthed Equipotential Bonding and Automatic Disconnection).

* Many 1950s and earlier earlier TT installations in the UK may lack this important safety feature. Non-EEBAD installations are capable of the whole installation CPC (Circuit Protective Conductor) remaining live for extended periods under fault conditions, which is a real danger.

* In TN-S and TT systems (and in TN-C-S beyond the point of the split), a residual-current device can be used as an additional protection. In the absence of any insulation fault in the consumer device, the equation "I"L1+"I"L2+"I"L3+"I"N = 0 holds, and an RCD can disconnect the supply as soon as this sum reaches a threshold (typically 10-500 mA). An insulation fault between either L or N and PE will trigger an RCD with high probability.

* In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering from contact between earth conductors of circuits on different RCDs or with real ground, thus making their use impracticable. Also, RCDs usually isolate the neutral core. Since it is unsafe to do this in a TN-C system, RCDs on TN-C should be wired to only interrupt the live conductor.

* In single-ended single-phase systems where the Earth and neutral are combined (TN-C, and the part of TN-C-S systems which uses a combined neutral and earth core), if there is a contact problem in the PEN conductor, then all parts of the earthing system beyond the break will rise to the potential of the L conductor. In an unbalanced multi-phase system, the potential of the earthing system will move towards that of the most loaded live conductor. Therefore, TN-C connections must not go across plug/socket connections or flexible cables, where there is a higher probability of contact problems than with fixed wiring. There is also a risk if a cable is damaged, which can be mitigated by the use of concentric cable construction and/or multiple earth electrodes. Due to the (small) risks of the lost neutral, use of TN-C-S supplies is banned for caravans and boats in the UK, and it is often recommended to make outdoor wiring TT with a separate earth electrode.

* In IT systems, a single insulation fault is unlikely to cause dangerous currents to flow through a human body in contact with earth, because no low-impedance circuit exists for such a current to flow. However, a first insulation fault can effectively turn an IT system into a TN system, and then a second insulation fault can lead to dangerous body currents. Worse, in a multi-phase system, if one of the live conductors made contact with earth, it would cause the other phase cores to rise to the phase-phase voltage relative to earth rather than the phase-neutral voltage. IT systems also experience larger transient overvoltages than other systems.

* In TN-C and TN-C-S systems, any connection between the combined neutral-and-earth core and the body of the earth could end up carrying significant current under normal conditions, and could carry even more under a broken neutral situation. Therefore, main equipotential bonding conductors must be sized with this in mind; use of TN-C-S is inadvisable in situations such as petrol stations, where there is a combination of lots of buried metalwork and explosive gases.

* In TN-C and TN-C-S systems, any break in the combined neutral-and-earth core which didn't also affect the live conductor could theoretically result in exposed metalwork rising to near "live" potential!

Electromagnetic compatibility

* In TN-S and TT systems, the consumer has a low-noise connection to earth, which does not suffer from the voltage that appears on the N conductor as a result of the return currents and the impedance of that conductor. This is of particular importance with some types of telecommunication and measurement equipment.

* In TT systems, each consumer has its own high-quality connection with earth, and will not notice any currents that may be caused by other consumers on a shared PE line.

Regulations

* In residential and commercial installations in the U. S. and Canada, the feed from the distribution transformer uses a combined neutral and grounding conductor (two phase and one neutral, for three wires total), but within the structure separate neutral and protective earth conductors are used (TN-C-S). The neutral must be connected to the earth (ground) conductor only on the supply side of the customer's disconnecting switch. Additional connections of neutral to ground within the customer's wiring are prohibited.

* For wiring less than 1000 V, the United States National Electrical Code and Canadian electrical code forbid the use of systems that combine the grounding conductor and neutral beyond the customer's disconnecting switch. Exemptions are made for certain appliances, such as: electric clothes dryers, and electric stoves.

* In Argentina, France (TT) and Australia (TN-C-S), the customer must provide their own ground connection.

* Japan is governed by PSE law.

Application examples

* Most modern homes in Europe have a TN-C-S earthing system. The combined neutral and earth occurs between the nearest transformer substation and the service cut out (the fuse before the meter). After this, separate earth and neutral cores are used in all the internal wiring.
* Older urban and suburban homes in the UK tend to have TN-S supplies, with the earth connection delivered through the lead sheath of the underground lead-and-paper cable.

* Some older homes, especially those built before the invention of residual-current circuit breakers and wired home area networks, use an in-house TN-C arrangement. This is no longer recommended practice.

* Laboratory rooms, medical facilities, construction sites, repair workshops, mobile electrical installations, and other environments that are supplied via engine-generators where there is an increased risk of insulation faults, often use an IT earthing arrangement supplied from isolation transformers. To mitigate the two-fault issues with IT systems, the isolation transformers should supply only a small number of loads each and/or should be protected with an insulation monitoring device (generally used only by medical or military IT systems, because of cost).

* In remote areas, where the cost of an additional PE conductor outweighs the cost of a local earth connection, TT networks are commonly used in some countries, especially in older properties. TT supplies to individual properties are also seen in mostly TN-C-S systems where an individual property is considered unsuitable for TN-C-S supply (e.g. petrol stations).

* In Australia, the TN-C-S system is in use; however, the wiring rules currently state that, in addition, each customer must provide a separate connection to earth via both a water pipe bond (if metallic water pipes enter the consumer's premises) and a dedicated earth electrode. In older installations, it is not uncommon to find only the water pipe bond, and it is allowed to remain as such, but the additional earth electrode must be installed if any upgrade work is done. The protective earth and neutral conductors are combined until the consumer's neutral link (located on the customer's side of the electricity meter's neutral connection) - beyond this point, the protective earth and neutral conductors are separate.

ee also

* Ground (electricity)
* Ground and neutral
* Electrical wiring

References

* IEC 60364-1: Electrical installations of buildings — Part 1: Fundamental principles, assessment of general characteristics, definitions. International Electrotechnical Commission, Geneva.
* Geoff Cronshaw: [http://www.iee.org/Publish/WireRegs/WiringMatters/Documents/Issue16/2005_16_autumn_wiring_matters_earthing_your_questions_answered.pdf Earthing: Your questions answered] . IEE Wiring Matters, Autumn 2005.
*Merlin Gerin Guide, Section 2.3: [http://www.electrical-installation.merlingerin.com/guide/pdf_files/E21-22.pdf Characteristics of TT, TN and IT systems] .
*John Whitfield: The Electricians Guide to the 16th Edition IEE Regulations, Section 5.2: [http://www.tlc-direct.co.uk/Book/5.2.1.htm Earthing systems] , 5th edition.


Wikimedia Foundation. 2010.

Игры ⚽ Нужна курсовая?

Look at other dictionaries:

  • Dust reduction system — mergeto: see below A dust spot caused by a dust particle on the image sensor A dust reduction system, or dust removal system, is a technology employed by several manufacturers of digital system cameras (often referred to …   Wikipedia

  • ГОСТ Р МЭК 60050-826-2009: Установки электрические. Термины и определения — Терминология ГОСТ Р МЭК 60050 826 2009: Установки электрические. Термины и определения оригинал документа: ( длительный ) допустимый ток ((continuous) current carrying capacity ampacity (US)): Максимальное значение электрического тока, который… …   Словарь-справочник терминов нормативно-технической документации

  • Ground (electricity) — In electrical engineering, ground or earth may be the reference point in an electrical circuit from which other voltages are measured, or a common return path for electric current, or a direct physical connection to the Earth. A typical earthing… …   Wikipedia

  • Ground and neutral — For uses of the term ground or earth in electricity but not in the context of mains wiring, see ground (electricity). Since the neutral point of an electrical supply system is often connected to earth ground, ground and neutral are closely… …   Wikipedia

  • Consumer mains wiring — Đomestic consumer mains wiring refers to the wiring in the house hold premises and low voltage installations. Even though arbitrary electric wiring demands detailed calculations for selection of conductor sizes, circuit breakers, voltage drops… …   Wikipedia

  • Earth leakage circuit breaker — An Earth Leakage Circuit Breaker (ELCB) is a safety device used in electrical installations with high earth impedance to prevent shock.PurposeMany electrical installations have a relatively high earth impedance. This may be due to the use of a… …   Wikipedia

  • заземляющее устройство — совокупность заземлителя и заземляющих проводников [ПУЭ] заземляющее устройство Нрк. система заземления Совокупность всех электрических соединений и устройств, обеспечивающих заземление системы, установки и оборудования [ГОСТ Р МЭК 60050 826… …   Справочник технического переводчика

  • Mains electricity by country — This article includes a list of countries and territories, with the plugs, voltages and frequencies they use for providing electrical power to small appliances and some major appliances. For definitions of terms and further information on each… …   Wikipedia

  • заземляющее устройство — 49 заземляющее устройство Совокупность электрически соединенных заземлителя и заземляющих проводников 604 04 02* de Erdungsanlage en earthing system, grounding system (USA) fr installation de mise à la terre Источник: ГОСТ 24291 90: Электрическая …   Словарь-справочник терминов нормативно-технической документации

  • Electrical bonding — is the practice of intentionally electrically connecting all metallic non current carrying items in a room or building as protection from electric shock. If a failure of electrical insulation occurs, all metal objects in the room will have the… …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”