Earth potential rise

Earth potential rise

In electrical engineering, Earth Potential Rise (EPR) also called Ground Potential Rise (GPR) occurs when a large current flows to earth through an earth grid impedance. The potential relative to a distant point on the Earth is highest at the point where current enters the ground, and declines with distance from the source. Ground potential rise is a concern in the design of electrical substations because the high potential may be a hazard to people or equipment. The potential gradient (drop of voltage with distance) may be so high that a person could be injured due to the voltage developed between two feet, or between the ground on which the person is standing and a metal object. Any conducting object connected to the substation earth ground, such as telephone wires, rails, fences, or metallic piping, may also be energized at the ground potential in the substation. This transferred potential is a hazard to people and equipment outside the substation.

Causes

Earth Potential Rise (EPR) is caused by electrical faults that occur at electrical substations, power plants, or high-voltage transmission lines. Short-circuit current flows through the plant structure and equipment and into the grounding electrode at station. The resistance of the Earth is finite, so current injected into the earth at the grounding electrode produces a potential rise with respect to a distant reference point. The resulting EPR or GPR can cause hazardous voltage in the form of Step & Touch Potentials, many hundreds of feet away from the actual fault location. Many factors determine the level of hazard, including: soil conditions, clearing time, and the amount of current entering the earth.

afety

EPR, along with other interference phenomena such as low frequency induction, is a safety issue in the coordination of power and telecommunications services. An EPR event at a site such as an electrical distribution substation may expose telecommunications personnel, users or plant to hazardous voltages.

The US Occupational Safety and Health Administration (OSHA) has designated EPR as a "known hazard" and has issued regulations governing the elimination of this hazard in the work place. [ 29 CFR 1910.269, with a specific addition under Appendix C. http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=9868 ]

tep and Touch Potentials

"Step potential" is the voltage between the feet of a person standing near an energized grounded object. It is equal to the difference in voltage, given by the voltage distribution curve, between two points at different distances from the "electrode". A person could be at risk of injury during a fault simply by standing near the grounding point.

"Touch potential" is the voltage between the energized object and the feet of a person in contact with the object. It is equal to the difference in voltage between the object (which is at a distance of 0 feet) and a point some distance away. The touch potential could be nearly the full voltage across the grounded object if that object is grounded at a point remote from the place where the person is in contact with it. For example, a crane that was grounded to the system neutral and that contacted an energized line would expose any person in contact with the crane or its uninsulated load line to a touch potential nearly equal to the full fault voltage.

Mitigation

OSHA 29 CFR 1910.269 Appendix C states that "Protection From the Hazards of Ground-Potential Gradients" requires an engineering analysis of the power system under fault conditions can be used to determine whether or not hazardous step and touch voltages will develop. The result of this analysis can ascertain the need for protective measures and can guide the selection of appropriate precautions.

Several methods may be used to protect employees from hazardous ground-potential gradients, including equipotential zones, insulating equipment, and restricted work areas.

1. The creation of an equipotential zone will protect a worker standing within it from hazardous step and touch potentials. Such a zone can be produced through the use of a metal mat connected to the grounded object. In some cases, a grounding grid can be used to equalize the voltage within the grid. Equipotential zones will not, however, protect employees who are either wholly or partially outside the protected area. Bonding conductive objects in the immediate work area can also be used to minimize the potential between the objects and between each object and ground. (Bonding an object outside the work area can increase the touch potential to that object in some cases, however.)

2. The use of insulating equipment, such as rubber gloves, can protect employees handling grounded equipment and conductors from hazardous touch potentials. The insulating equipment must be rated for the highest voltage that can be impressed on the grounded objects under fault conditions (rather than for the full system voltage).

3. Restricting employees from areas where hazardous step or touch potentials could arise can protect employees not directly involved in the operation being performed. Employees on the ground in the vicinity of transmission structures should be kept at a distance where step voltages would be insufficient to cause injury. Employees should not handle grounded conductors or equipment likely to become energized to hazardous voltages unless the employees are within an equipotential zone or are protected by insulating equipment.

Calculations

In principle, the potential of the earth grid Vgrid can be calculated using Ohm's Law if the fault current (If) and resistance of the grid (Zgrid) are known.: mathbf{V}_{grid} = mathbf{I}_f imes mathbf{Z}_{grid}

While the fault current from a distribution or transmission system can usually be calculated or estimated with precision, calculation of the earth grid resistance is more complicated. Difficulties in calculation arise from the extended and irregular shape of practical ground grids, and the varying resistivity of soil at different depths.

At points outside the earth grid, the potential rise decreases. The simplest case of the potential at a distance is the analysis of a driven rod electrode in homogeneous earth. The voltage profile is given by the following equation.:mathbf{V}_{r} = frac{mathbf{ ho I{mathbf{2 pi r_xwhere:mathbf{r_x} is a point beyond the edge of the earth grid.:mathbf{V}_{r} is the voltage at distance mathbf{r_x} from the earth grid, in volts.:mathbf{ ho} is the resistivity of the earth, in Ω·m.:mathbf{I} is the earth fault current, in amperes.This case is a simplified system; most earthing systems are more complex than a single rod, and the soil will have varying resistivity. It can, however, reliably be said that the resistance of a ground grid is inversely proportional to the area it covers; this rule can be used to quickly assess the degree of difficulty for a particular site.

tandards & Regulations

US Federal Law [ under 29 CFR 1910.269 ] mandates the elimination of hazardous voltages created by EPR, such as Step & Touch Potentials, in the work place.

IEEE Std. 80-2000 is a standard that addresses the mitigation of Step & Touch Potentials to acceptable levels. It has become widely applied for EPR mitigation.

ee also

* High Voltage Isolation and Ground Potential Rise

References

[1] ACIF Working Committee CECRP/WC18, "AS/ACIF S009:2006 Installation Requirements for Customer Cabling (Wiring Rules)", Australian Communications Industry Forum, North Sydney, Australia (2006) ISBN 1-74000-354-3

External links

* http://www.acif.org.au/__data/page/15836/S009_2006r.pdf AS/ACIF S009:2006 Installation Requirements for Customer Cabling (Wiring Rules).
*http://esgroundingsolutions.com/ Information about Ground Potential Rise Studies
*http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=9868 OSHA 29 CFR 1910.269


Wikimedia Foundation. 2010.

Игры ⚽ Поможем решить контрольную работу

Look at other dictionaries:

  • Ground Potential Rise — Articles on Ground Potential Rise include: * Earth potential rise * High Voltage Isolation and Ground Potential Rise …   Wikipedia

  • High Voltage Isolation and Ground Potential Rise — This article outlines the principles of High Voltage Isolation (HVI) and Ground Potential Rise (GPR). Most often questions of concern arise to anyone associated with the use of any communication signal (analog or digital) via a metallic or fiber… …   Wikipedia

  • Earth Hour — is an annual international event created by WWF (The World Wide Fund for Nature/World Wildlife Fund), held on the last Saturday of March, that asks households and businesses to turn off their non essential lights and electrical appliances for one …   Wikipedia

  • Single-wire earth return — (SWER) or single wire ground return is a single wire transmission line for supplying single phase electrical power from an electrical grid to remote areas at low cost. It is principally used for rural electrification, but also finds use for… …   Wikipedia

  • Earth Sciences — ▪ 2009 Introduction Geology and Geochemistry       The theme of the 33rd International Geological Congress, which was held in Norway in August 2008, was “Earth System Science: Foundation for Sustainable Development.” It was attended by nearly… …   Universalium

  • Earth's magnetic field — Computer simulation of the Earth s field in a normal period between reversals.[1] The tubes represent magnetic field lines, blue when the field points towards the center and yellow when away. The rotation axis of the Earth is centered and… …   Wikipedia

  • Potential energy — This article is about a form of energy in physics. For the statistical method, see Potential energy statistics. Classical mechanics Newton s Second Law …   Wikipedia

  • Rise of Rome — The rise of Rome to dominate the overt politics of Europe, North Africa and the Near East completely from the 1st century BC to the 4th century AD, is the subject of a great deal of analysis by historians, military strategists, political… …   Wikipedia

  • Earth exploration — Introduction   the investigation of the surface of the Earth and of its interior.  By the beginning of the 20th century most of the Earth s surface had been explored, at least superficially, except for the Arctic and Antarctic regions. Today the… …   Universalium

  • Rise of Nations — Infobox VG title = Rise of Nations developer = Big Huge Games publisher = Microsoft Game Studios designer = Brian Reynolds engine = version = 02.04.04.2903 released = vgrelease|North America|NA|May 20, 2003 vgrelease|Europe|EU|May 23, 2003 genre …   Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”