- Thermal transmittance
Thermal transmittance, also known as
U-value , is the rate of transfer of heat (inwatt s) through one squaremetre of a structure divided by the difference in temperature across the structure. It is expressed in watts per square metre per kelvin, or W/m²K. Well-insulated parts of abuilding have a low thermal transmittance whereas poorly-insulated parts of a building have a high thermal transmittance.:Φ = A × U × (T1 - T2)
where Φ is the heat transfer in watts, U is the thermal transmittance, T1 is the
temperature on one side of the structure, T2 is thetemperature on the other side of the structure and A is thearea in squaremetre s.Thermal transmittances
of most walls and roofs can be calculated using ISO 6946, unless there is metal bridging the insulation in which case it can be calculated using ISO 10211. For most groundfloors it can be calculated using ISO 13370. For mostwindow s the thermal transmittance can be calculated using ISO 10077 or ISO 15099. ISO 9869 describes how to measure the thermal transmittance of a structure experimentally.Typical thermal transmittance values for common building structures are as follows:
*single glazing: 5.7 W/m²K;
*single glazed windows, allowing for frames: 4.5 W/m²K;
*double glazed windows, allowing for frames: 3.3 W/m²K;
*double glazed windows with advanced coatings: 2.2 W/m²K;
*triple glazed windows, allowing for frames: 1.8 W/m²K;
*well-insulated roofs: 0.15 W/m²K;
*poorly-insulated roofs: 1.0 W/m²K;
*well-insulated walls: 0.25 W/m²K;
*poorly-insulated walls: 1.5 W/m²K;
*well-insulated floors: 0.2 W/m²K;
*poorly-insulated floors: 1.0 W/m²K;In practice the thermal transmittance is strongly affected by the quality of workmanship and if insulation is fitted poorly, the thermal transmittance can be considerably higher than if insulation is fitted well.
Calculating thermal transmittance
When calculating a thermal transmittance it is helpful to consider the building's construction in terms of its different layers. For instance a cavity wall might be described as in the following table:
In this example the total resistance is 1.64 m²K/W. The thermal transmittance of the structure is the
reciprocal of the total thermal resistance. The thermal transmittance of this structure is therefore 0.61 W/m²K.(Note that this example is simplified as it does not take into account any metal connectors, air gaps interrupting the insulation or mortar joints between the bricks and concrete blocks.)
It is possible to allow for mortar joints in calculating the thermal transmittance of a wall, as in the following table. Since the mortar joints allow heat to pass more easily than the light concrete blocks the mortar is said to "bridge" the light concrete blocks.
The average thermal resistance of the "bridged" layer depends upon the fraction of the area taken up by the mortar in comparison with the fraction of the area taken up by the light concrete blocks. To calculate thermal transmittance when there are "bridging" mortar joints it is necessary to calculate two quantities, known as "Rmax" and "Rmin".Rmax can be thought of as the total thermal resistance obtained if it is assumed that there is no lateral flow of heat and Rmin can be thought of as the total thermal resistance obtained if it is assumed that there is no resistance to the lateral flow of heat.The U-value of the above construction is approximately equal to 2 / (Rmax + Rmin)Further information about how to deal with "bridging" is given in
ISO 6946 .Measuring thermal transmittance
Whilst calculation of thermal transmittance can readily be carried out with the help of software which is compliant with ISO 6946, a thermal transmittance calculation does not fully take workmanship into account and it does not allow for adventitious circulation of air between, through and around sections of insulation. To take the effects of workmanship-related factors fully into account it is necessary to carry out a thermal transmittance measurement.
ISO 9869 describes how to measure the thermal transmittance of a roof or a wall by using heat
flux meters. These heat flux meters usually consist of thermopiles which provide an electrical signal which is in direct proportion to the heat flux. Typically they might be about 100 mm in diameter and perhaps about 5 mm thick and they need to be fixed firmly to the roof or wall which is under test in order to ensure good thermal contact. When the heat flux is monitored over a sufficiently long time, the thermal transmittance can be calculated by dividing the average heat flux by the average difference in temperature between the inside and outside of the building. For most wall and roof constructions the heat flux meter needs to monitor heat flows (and internal and external temperatures) continuously for periods of around two weeks at least. For ground floors the heat flux meters may need to be left in place for over a year (due to the massive heat storage in the ground).Generally, thermal transmittance measurements are most accurate when:
*The difference in
temperature between the inside and outside of the building is large.
*The weather is cloudy rather than sunny (this makes accurate measurement of temperature easier).
*There is good thermal contact between the heat flux meter and the wall or roof being tested.
*The monitoring of heat flow and temperatures is carried out over a long period of time.
*Several spot measurement points are used rather than just one or two.References
*Field investigations of the thermal performance (U-values) of construction elements as built [http://projects.bre.co.uk/uvalues/U-values.pdf]