15 kV AC

15 kV AC

The 15 kV AC 16⅔ Hz railway electrification system is used in Germany, Austria, Switzerland, Sweden, and Norway. The high voltage enables high power transmission with low losses, while the lower frequency reflects technical limitations at the turn of the 20th century. In particular, the lower frequency reduces flashover problems in the motors, although at the cost of a non-standard line frequency requiring frequency conversion and separate supplies. 16⅔ hertz is equivalent 1000 rpm. In 1995 the standard was altered to 16.7 Hz, although 16⅔ Hz is within the tolerance.

Distribution Networks

In Germany (except Mecklenburg-Western Pomerania and Saxony-Anhalt), Austria and Switzerland, there are special power grids for single phase AC current at16.7 Hz; the voltage of these grids is 110 kV in Germany and Austria, 132 kV in Switzerland. This system is called centralized railway energy supply.

In Sweden, Norway, Mecklenburg-Western Pomerania and Saxony-Anhalt, there are no special single phase power grids, but the energy is taken directly from the three phase grid (110 kV at 50 Hz), inverted and fed into the overhead line. This system is called decentralized railway energy supply.

Generation

There are two possibilities to supply the centralized system with electricity; the energy is either provided by a special power plant, that generates 110(132) kV, 16.7 Hz, or the energy is taken, similar to the decentralized system, from the national power grid (110 kV, 50 Hz), but inverted into 110(132) kV, 16.7 Hz by rotary machines or static inverters, then distributed throughout the country. The middle of these power lines is grounded by a coil, so each conductor of an 110(132)kV power line for single phase AC has a voltage of 55 (66) kV against ground. The coil over which the grounding is done is designed to compensate ground error currents in case of a defect of the line. At the transformer stations the voltage is transformed from 110(132) kV to 15 kV and the energy is fed into the overhead line. The frequency of 16.7 Hz depends on the necessity to avoid synchronism in parts of the rotary machine, which consists principally of a three phase asynchronous motor and a one phase synchronous generator. Since synchronism sets in at a frequency of 16⅔ Hz (according to the technical details) in the one phase system, the frequency of the centralized system was set to 16.7 Hz.

Power plants providing 110 kV, 16.7 Hz, are either exclusively producing single phase AC or have special generators, such as the nuclear power plant in Neckarwestheim or the Walchensee Powerstation.

The power for the decentralized system is taken directly from the national power grid and directly transformed and inverted into 15 kV, 16⅔ Hz by synchronous-synchronous-converters or static inverters. Both systems need additional transformers. The converters consist of a three phase synchronous motor and a one phase synchronous generator. The decentralized system in the north-east of Germany was established by the Deutsche Reichsbahn in the 1980s, because there was no centralized system available in these areas.

The 25 kV AC system is now the norm for new railway electrifications, but extensions of existing the 15 kV networks are likely; none of the five countries that use the system have made any indications that they are going to convert to a 25 kV AC system.

See also

* Alternating current (AC)
* List of current systems for electric rail traction
*

External links

* [http://www.udo-leuschner.de/energie-chronik/030808.htm DB Energie soll Durchleitung von Bahnstrom ermöglichen] de icon


Wikimedia Foundation. 2010.

Игры ⚽ Поможем написать реферат