Confusing|date=December 2007 Cleanup|date=December 2007 Unreferenced|date=December 2007 The Main Distribution Area includes the main cross-connect (MC), which is the central point of distribution for the
data center structured cabling system and may includehorizontal cross- connect (HC) when equipment areas are served directly from the main distribution area. This space is inside thecomputer room ; it may be located in a dedicated room in a multi-tenant data center for security. Every data center shall have at least one main distribution area. The computer room corerouter s, coreLAN switches , core SAN switches, and PBX are often located in the main distribution area, because this space is thehub of the cabling infrastructure for the data center. Access provider provisioning equipment (for example the M13 multiplexers) is often located in the main distribution area rather than in the entrance room to avoid the need for a second entrance room due to circuit length restrictions. The main distribution area may serve one or more horizontal distribution areas or equipment distribution areas within the data center and one or more telecommunications rooms located outside the computer room space to support office spaces, operations center and other external support roomsreference:
* [http://www.adc.com/Library/Literature/102264AE.pdf TIA-942:Data Center Standards Overview]