- Snubber
A snubber is a device used to suppress ("snub") voltage transients in electrical systems, pressure transients in fluid systems, or excess force or rapid movement in mechanical systems.
Fluid systems
Mechanical systems
A snubber can be a mechanical device that limits pressure or velocity surges on measurement devices. These connect between the process and the measurement device allowing a relatively slow change in pressure or velocity to limit damage to the hardware. Such devices are common in industrial environments.
Electrical systems
Snubbers are frequently used in electrical systems with an inductive load where the sudden interruption of current flow would lead to a sharp rise in
voltage across the device creating the interruption. This sharp rise in voltage might lead to a transient or permanent failure of the controlling device. A spark is likely to be generated (arcing) and to causeelectromagnetic interference . The snubber prevents this undesired voltage by conducting transient current around the device.RC snubbers
s. The voltage across a capacitor cannot change instantaneously, so a decreasing transient current will flow through it for a small fraction of a second, allowing the voltage across the switch to increase more slowly. While the values can be optimised for the application, a 100 ohm resistor in series with a 100 nanofarad capacitor of appropriate voltage rating is usually effective. This type of snubber is often manufactured as a single component.
Diode snubbers
When the current flowing is DC, a simple rectifier
diode is often employed as another form of snubber. The snubber diode is wired in parallel with an inductive load (such as arelay coil orelectric motor ). The diode is installed so that it does not conduct under normal conditions. When current to the inductive load is rapidly interrupted, a large voltage spike would be produced in the reverse direction (as the inductor attempts to keep current flowing in the circuit). This spike is known as an "inductive kick ". Placing the snubber diode in inverse parallel with the inductive load allows the current from the inductor to flow through the diode rather than through the switching element, dissipating the energy stored in the inductive load over the series resistance of the inductor and the (usually much smaller) resistance of the diode (over-voltage protection). One disadvantage of simple rectifier diode used as a snubber is that the diode allows current to continue flowing, which may cause the relay to remain actuated for slightly longer; some circuit designs must account for this delay in the "dropping-out" of the relay.More-sophisticated solid-state snubbers
In some dc circuits, a
varistor or two inverse-seriesZener diode s (collectively called a transorb) may be used instead of the simple diode. Because these devices dissipate significant power, the relay may drop-out faster than it would with a simple rectifier diode. An advantage to using a transorb over just one diode however, is that it will protect against both over and under voltage if connected to ground, forcing the voltage to stay between the confines of the breakdown voltages of the Zener diodes. Just one Zener diode connected to ground will only protect against positive transients.In ac circuits a rectifier diode snubber cannot be used; if a simple RC snubber is not adequate a more complex bidirectional snubber design must be used.
See also
*
Transient voltage suppression diode
*Transil
Wikimedia Foundation. 2010.