High leg delta

High leg delta

A high leg delta (also known as wild-leg or red-leg delta) is a type of electrical service connection sometimes found in older three-phase electric power installations.

This type of service is supplied by a transformer having four wires coming out of the secondary: the three phases, plus a neutral that is used to center-tap one of the windings. The voltages between the three phases are the same in magnitude, however the voltage magnitudes between a particular phase and the neutral vary. The phase-to-neutral voltage of two of the phases will be half of the phase-to-phase voltage. The remaining phase-to-neutral voltage will be √3 times half the phase-to-phase voltage. Typically, the transformer is connected such that the 'B' phase is the 'high' leg. According to Article 110.15 of the 2005 National Electrical Code, panelboards connected to this type of transformer must explicitly identify the high leg, preferably by coloring it orange.

Example

Consider the low voltage side of a 480/240 V high leg delta connected transformer, where the 'B' phase is the 'high' leg. The line to line voltages are all the same:

V_{ab} = V_{bc} = V_{ac} = 240 V

Because the winding between the 'A' and 'C' phases is center-tapped, the line-to-neutral voltages for these phases are as follows:

V_{an} = V_{cn} = 120 V

But the phase-neutral voltage for the 'B' phase is different:

V_{bn} = 120sqrt{3} V approx 208 V

This can be proven by writing a KVL equation starting from the grounded neutral:

0 + 120 angle 0^circ + 240 angle 120^circ = 120sqrt{3} angle 90^circ

Note: Writing the KVL equation going the other way, the same magnitude is found, though the phase angle will of course be different.

Advantages

This type of services is usually supplied using 240V line-to-line and 120V phase to neutral. In some ways, the high leg delta service provides the best of both worlds: a line-to-line voltage that is higher than the usual 208V that most three-phase services have, and a line-to-neutral voltage (on two of the phases) sufficient for connecting appliances and lighting. Thus, large pieces of equipment will draw less current than with 208V, requiring smaller wire and breaker sizes. Lights and appliances requiring 120V can be connected to phases 'A' and 'C' without requiring an additional step-down transformer.

Disadvantages

Since one phase-to-neutral voltage (phase 'B') is higher than the others, no single phase loads can be connected to this phase. This essentially eliminates one third of the breakers in a panel if there are many single-phase loads.

References

*http://www.sea.siemens.com/step/templates/lesson.mason?pan:3:2:3
*NFPA 70: National Electrical Code, 2005 Ed.


Wikimedia Foundation. 2010.

Игры ⚽ Поможем решить контрольную работу

Look at other dictionaries:

  • Delta — commonly refers to: Delta (letter), Δ or δ in the Greek alphabet, also used as a mathematical symbol River delta, a landform at the mouth of a river Delta Air Lines, a major U.S. airline Delta may also refer to: Contents 1 Places …   Wikipedia

  • Delta-wye transformer — Not to be confused with Y Δ transform. A delta wye (Δ Y) transformer is a transformer that converts three phase electric power without a neutral wire into 3 phase power with a neutral wire. It can be a single three phase transformer, or built… …   Wikipedia

  • Delta robot — Sketchy, a portrait drawing delta robot[1] A delta robot is a type of parallel robot. It consists of three arms connected to universal joints at the base. The key design feature is the use of parallelograms in the arms, which maintains the… …   Wikipedia

  • Captain Shreve High School — (CSHS) is a magnet high school located in Shreveport, Louisiana. Captain Shreve High School was opened in the fall of 1967. The school was named for Captain Henry Miller Shreve, who was responsible for clearing the log jam on the Red River which… …   Wikipedia

  • Tropical Storm Delta (2005) — Infobox Hurricane Name=Tropical Storm Delta Type=Tropical Storm Year=2005 Basin=Atl Image location=Ts delta 112405.jpg Formed=November 22, 2005 Dissipated=November 29, 2005 1 min winds=60 Pressure=980 Da Inflated=0 Fatalities=7 direct, 12 missing …   Wikipedia

  • Split-phase electric power — A split phase electricity distribution system is a 3 wire single phase distribution system, commonly used in North America for single family residential and light commercial (up to about 100 kVA) applications. It is the AC equivalent of the… …   Wikipedia

  • Einphasen-Dreileiternetz — Schaltung eines Ortstransformators in einem Einphasen Dreileiternetz …   Deutsch Wikipedia

  • Transformer types — Circuit symbols Transformer with two windings and iron core. Step down or step up transformer. The symbol shows which winding has more turns, but not usually the …   Wikipedia

  • Electrical wiring (United States) — Electrical wiring in general refers to conductors used to carry electricity and their accessories. General aspects of electrical wiring as used to provide power in or to buildings and structures, commonly referred to as building wiring, are… …   Wikipedia

  • IEC 60309 — DIN EN 60309 Bereich Elektrotechnik Titel Stecker, Steckdosen und Kupplungen für industrielle Anwendungen Kurzbesch …   Deutsch Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”