Lumen method

Lumen method

Also known as the zonal cavity method, the lumen method is a series of calculations that uses horizontal illuminance criteria to establish a uniform luminaire layout in a space. In its simplest form, the lumen method is merely the total number of lumens available in a room divided by the area of the room [cite web|url=http://www.lightcalc.com/glossary.html|title= Light Calc|work= Glossary|accessdate=2008-03-20] . In order to perform this calculation, many factors, coefficients, lamp lumen data and other quantities must be gathered. Despite the scientific impression of the lumen method equations, there are inaccuracies and assumptions built into the method. Therefore, the lumen method should not typically be used as a standalone, final solution; it should be used as a tool in particularly uniform settings of lighting design if a simple, rough technique of illuminance quantification is desired.Steffy, LC, IES, FIALD, Gary 1963. "Architectural Lighting Design, 2nd edition" John Wiley & Sons, Inc., New York]

Method

For a step-by-step guide, reference the IESNA Lighting Handbook [Rea, PH. D., FIES, Mark S., Illuminating Engineering Society of North America (2000), "The IESNA Lighting Handbook", 9th edition, 8-11 to 8-14] .

The lumen method is outlined in the table:Figure 1: Table 10.2 Lumen method Variables and Formulations (Steffy 2002).

Usage

As seen from Figure 1, the lumen method can be manipulated to output a particular variable. This is valuable because certain numbers are needed at different times in the design process. “Number of luminaires” is important because this number can be used to estimate costs and layout the spacing of luminaires in a computer lighting calculation program (Steffy 2002).

Variables

The CU value should be obtained by the manufacturer of the luminaire which is to be evaluated. In order to determine the CU on the manufacturer’s table, a room cavity ratio (RCR) must be used. Also, the reflectance of the ceiling, walls and floor must be known.

RCR = 5 x (room height) x (room width + room length) / [(room width) x (room length)] [Hughes, S. David (1988), "Electrical Systems in Buildings", 150, Delmar Publishers Inc]

Lumens per lamp should be obtained from the lamp manufacturer.

Light Loss Factors can be calculated using methods in the IESNA handbook. Sometimes, individual companies have their own rule of thumb for Light Loss Factors. The ballast factor can be obtained from the ballast manufacturer.

References


Wikimedia Foundation. 2010.

Игры ⚽ Поможем написать курсовую

Look at other dictionaries:

  • Lumen (unit) — The lumen (symbol: lm) is the SI unit of luminous flux, a measure of the perceived power of light. Luminous flux differs from radiant flux, the measure of the total power of light emitted, in that luminous flux is adjusted to reflect the varying… …   Wikipedia

  • Glucose uptake — Method of glucose uptake differs throughout tissues depending on two factors; the metabolic needs of the tissue and availability of glucose. The two ways in which glucose uptake can take place are facilitated diffusion (a passive process) and… …   Wikipedia

  • Atheroma — Classification and external resources Atherosclerotic plaque from a carotid endarterectomy specimen. This shows the bifurcation of the common into the internal and …   Wikipedia

  • Tracheal intubation — Intervention Anesthesiologist using the Glidescope video laryngoscope to intubate the trachea of a morbidly obese elderly person with challenging airway anatomy …   Wikipedia

  • Atherosclerosis — For the journal, see Atherosclerosis (journal). Atherosclerosis Classification and external resources The progression of atherosclerosis (size exaggerated; see text) ICD 10 …   Wikipedia

  • digestive system disease — Introduction       any of the diseases that affect the human digestive tract. Such disorders may affect the esophagus, stomach, small intestine, large intestine (colon), pancreas, liver, or biliary tract. A prevalent disorder of the digestive… …   Universalium

  • Blut-Gehirn-Schranke — Die Blut Hirn Schranke, auch Blut Gehirn Schranke genannt, ist eine bei allen Landwirbeltieren (Tetrapoda) im Gehirn vorhandene physiologische Barriere zwischen dem Blutkreislauf und dem Zentralnervensystem. Sie dient dazu, die Milieubedingungen… …   Deutsch Wikipedia

  • Endotheliale Blut-Hirn-Schranke — Die Blut Hirn Schranke, auch Blut Gehirn Schranke genannt, ist eine bei allen Landwirbeltieren (Tetrapoda) im Gehirn vorhandene physiologische Barriere zwischen dem Blutkreislauf und dem Zentralnervensystem. Sie dient dazu, die Milieubedingungen… …   Deutsch Wikipedia

  • Gliale Blut-Hirn-Schranke — Die Blut Hirn Schranke, auch Blut Gehirn Schranke genannt, ist eine bei allen Landwirbeltieren (Tetrapoda) im Gehirn vorhandene physiologische Barriere zwischen dem Blutkreislauf und dem Zentralnervensystem. Sie dient dazu, die Milieubedingungen… …   Deutsch Wikipedia

  • Hirn-Blut-Schranke — Die Blut Hirn Schranke, auch Blut Gehirn Schranke genannt, ist eine bei allen Landwirbeltieren (Tetrapoda) im Gehirn vorhandene physiologische Barriere zwischen dem Blutkreislauf und dem Zentralnervensystem. Sie dient dazu, die Milieubedingungen… …   Deutsch Wikipedia

Share the article and excerpts

Direct link
Do a right-click on the link above
and select “Copy Link”