MAIFI

MAIFI

The Momentary Average Interruption Frequency Index (MAIFI) is a reliability indicator used by electric power utilities. MAIFI is the average number of momentary interruptions that a customer would experience during a given period (typically a year). Electric power utilities may define momentary interruptions differently, with some considering a momentary interruption to be an outage of less than 1 minute in duration while others may consider a momentary interruption to be an outage of less than 5 minutes in duration. MAIFI is calculated as

mbox{MAIFI} = frac{mbox{total number of customer interruptions less than the defined time{mbox{total number of customers served

MAIFI has tended to be less reported than other reliability indicators, such as SAIDI, SAIFI, and CAIDI. However, MAIFI is useful for tracking momentary power outages, or "blinks," that can be hidden or misrepresented by an overall outage duration index like SAIDI or SAIFI.

Momentary power outages are often caused by transient faults, such as lightning strikes or vegetation contacting a power line, and many utilities use reclosers to automatically restore power quickly after a transient fault has cleared.

ee also

*SAIDI
*SAIFI
*CAIDI
*CAIFI
*Autorecloser


Wikimedia Foundation. 2010.

Игры ⚽ Поможем сделать НИР

Look at other dictionaries:

  • SAIDI — The System Average Interruption Duration Index (SAIDI) is commonly used as a reliability indicator by electric power utilities. SAIDI is the average outage duration for each customer served, and is calculated as:mbox{SAIDI} = frac{mbox{sum of all …   Wikipedia

  • SAIFI — The System Average Interruption Frequency Index (SAIFI) is commonly used as a reliability indicator by electric power utilities. SAIFI is the average number of interruptions that a customer would experience, and is calculated asmbox{SAIFI} =… …   Wikipedia

  • CAIDI — The Customer Average Interruption Duration Index (CAIDI) is a reliability index commonly used by electric power utilities. It is related to SAIDI and SAIFI, and is calculated asmbox{CAIDI} = frac{mbox{sum of all customer interruption… …   Wikipedia

  • Outage management system — An Outage Management System (OMS) is a computer system used by operators of electric distribution systems to assist in restoration of power. Contents 1 Major Functions of an OMS 2 OMS Principles and Integration Requirements 3 OMS Benefits …   Wikipedia

  • CAIFI — The Customer Average Interruption Frequency Index (CAIFI)[1] is a popular index used in electrical reliability analysis.[2] It is designed to show trends in customers interrupted and helps to show the number of customers affected out of the whole …   Wikipedia